Parameters 415
(Only visible with a BCU control unit)
Selects which PSL2 channels on the BCU control unit are
connected to another BCU and routed to a local power unit.
Notes:
• The local power units are to be connected to successive
channels starting from CH1. The other BCU is then
connected to one or more successive channels starting
from the first free channel.
• The lowest channel selected in this parameter is routed to
the local power unit with the lowest number, etc.
• There must be at least as many local power modules as
there are routed channels.
• This parameter cannot be changed while the drive is
running.
See section
Router mode for BCU control unit
(page
0000h
0000h…FFFFh
Selection of routed BCU channels.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
ch1
0
1
ch2
1 = Channel CH2 is routed to the local power unit (which is
connected to CH1).
…
…
…
11
ch12
1 = Channel CH12 is routed to a local power unit.
12…15 Reserved