Quick start-up guide 11
Decanter I/O control connections
XPOW External power input
1
+24VI
24 V DC, 2 A
2
GND
XAI Reference voltage and analog inputs
1
+VREF
10 V DC, RL 1…10 kohm
2
-VREF
-10 V DC, RL1…10 kohm
3
AGND
Ground
4
AI1+
Analog input 1, 0(2)...10V
Speed ref (bowl)/Not in use (scroll)
5
AI1-
6
AI2+
By default not in use
0(4).....20 mA
7
AI2-
XAO
1
AO1
Actual motor speed (Act delta speed)
2
AGND
0...20 mA
3
AO2
Actual motor torque
4
AGND
0...20 mA
XD2D
1
B
Drive-to-drive link
2
A
3
BGND
XRO1
1
NC
Ready (No fault)
250 V AC / 30 VDC
2 A
2
COM
3
NO
1
NC
Running
250 V AC / 30 VDC
2 A
2
COM
3
NO
1
NC
Fault (-1)
250 V AC / 30 VDC
2 A
2
COM
3
NO
XD24
1
DIIL
Digital interlock
2
+24VD
+24 V DC 20 mA
3
DICOM
Digital input ground
4
+24VD
+24 V DC 200 mA
5
DIOGND
Digital input/output
XDIO
1
DIO1
Output: Ready
2
DIO2
Output: Running
XDI
1
DI1
Stop (0) / Start (1)
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
XSTO
Safe torque off circuits must be closed for the drive to
start. See Hardware manual of drive.
X12 Safety options connection
X13 Control panel connection
X205 Memory unit connection
*) The scroll drive calculates its
speed reference from the delta
speed reference and the bowl actual
speed. By default the delta speed is
given by a parameter, and the bowl
actual speed is received via the serial
link from the bowl drive.