Joining cabinet sections together
Wide cabinet line-ups are delivered in multiple sections. The sections are to be joined on-site
using a 200 mm wide joining cubicle at the end of one section (a common motor terminal
cubicle can also act as a joining cubicle). The screws required for the joining are enclosed
in a plastic bag inside the cabinet. The threaded bushings are already mounted on the
cabinet posts.
1.
Fasten the first section to the floor.
2.
Remove any plates covering the rear post of the joining cubicle.
3.
Slide Axilock connectors onto the coolant pipes at the joint.
4.
Align the two sections.
The coolant pipe ends must be aligned as shown.
5
…
15 mm (0.2
…
0.6")
< 2°
< 3 mm (0.12")
Mechanical installation 19