10 / uint16
Defines the light intensity of the transmission LED of
RDCO module channel CH2. (This parameter is effective
only when parameter
is
set to
. FDCO modules have a hardware
transmitter current selector.)
In general, use higher values with longer fiber optic
cables.
The maximum setting is applicable to the maximum
length of the fiber optic link. See
M/F link control
60.7
- / -
Light intensity.
1...15
100 ms / uint16
Sets a timeout for master/follower (DDCS)
communication. If a communication break lasts longer
than the timeout, the action specified by parameter
is taken.
As a rule of thumb, this parameter should be set to at
least 3 times the transmit interval of the master.
M/F comm loss
timeout
60.8
- / -
Master/follower communication timeout.
0...65535 ms
Fault / uint16
Selects how the drive reacts to a master/follower
communication break.
M/F comm loss
function
60.9
0
No action taken.
NoAction
1
The drive generates an
warning.
This only occurs if control is expected from the
master/follower link, or if supervision is forced using
parameter
60.32 M/F comm supervision force
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Warning
2
Drive trips on
. This only occurs if
control is expected from the master/follower link, or
if supervision is forced using parameter
.
Fault
3
Drive trips on
. This occurs even
though no control is expected from the master/follower
link.
Fault always
Auto / uint16
Selects the type and scaling of reference 1 received
from the master/follower link. The resulting value is
shown by
M/F ref1 type
60.10
0
Type and scaling are chosen automatically according
to which reference chain (see settings
,
,
) the incoming reference is connected to. If
the reference is not connected to any chain, no scaling
is applied (as with setting Transparent).
Auto
1
No scaling is applied.
2
Generic reference with a scaling of 100 = 1 (ie. integer
and two decimals).
3
The scaling is defined by parameter
.
Torque
Parameters 407
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...