Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Warning / uint16
Selects how the drive reacts when a main cooling fan
fault is detected.
Note: With an inverter unit consisting of one or more
frame R8i inverter modules with speed-controlled fans,
it may be possible to continue operation even if one
main fan of a module stops. When fan failure is
detected, the control program will automatically
•
set the other fan of the module to full speed
•
set the fans of the other modules (if any) to full
speed
•
decrease the switching frequency to a minimum,
and
•
disable the supervision of temperature difference
between the modules.
If this parameter is set to
, the inverter unit will
trip (but still carry out the actions listed above).
Otherwise, the inverter will attempt to continue
operation.
Main fan fault
function
31.35
0
The drive trips on fault
Fault
1
The drive generates an
Warning
2
No action taken.
No action
Fault / uint16
(Only visible with a ZCU control unit)
Selects how the drive reacts when a modules internal
auxiliary fan fault is detected.
Aux fan fault
function
31.36
0
The drive trips on fault
5081 Auxiliary fan not running
.
Note: The fault is suppressed for two minutes after
power-up.
During this time, the drive only generates a warning,
A582 Auxiliary fan not running
.
Fault
1
The drive generates a warning,
.
Warning
Parameters 325
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...