What to do
Cause
Event name /
Aux. code
Code
(hex)
The auxiliary code identifies the fan
(1: Auxiliary fan 1, 2: Auxiliary fan 2).
An auxiliary cooling fan (connected to
the fan connectors on the control unit)
is stuck or disconnected.
Auxiliary fan
not running
A582
Check that the auxiliary fan
supervision selection in parameter
matches the
hardware.
Make sure the front cover of the drive
module is in place and tightened.
Check auxiliary fan(s) and
connection(s).
Replace faulty fan.
Check safety circuit connections. For
more information, see appropriate
Safe torque off function is active, i.e.
safety circuit signal(s) connected to
connector XSTO is lost.
Safe torque
off
A5A0
drive hardware manual and
description of parameter
indication run/stop (page 320)
Check the auxiliary code (format XXXY
YYZZ). “Y YY” specifies through which
Problem with internal temperature
measurement of the drive.
Measurement
circuit
temperature
A5EA
BCU control unit channel the fault was
received (“0 00” with a ZCU control
unit).
“ZZ” specifies the location:
With control program version 2.8x and
later: 1: U-phase IGBT, 2: V-phase IGBT,
3: W-phase IGBT, 4: Power supply
board, 5: Power unit xINT board, 6:
Brake chopper, 7: Air inlet (TEMP3,
X10), 8: du/dt filter (TEMP2, X7), 9:
TEMP1 (X6).
With control program version up to
and including 2.7x: 1: U-phase IGBT, 2:
V-phase IGBT, 3: W-phase IGBT, 4:
Power unit INT board, 5: Brake
chopper, 6: Air inlet, 7: Power supply
board, 8: du/dt filter, FAh: Air in temp.
Contact your local ABB representative.
Power unit power supply failure.
PU board
powerfail
A5EB
Check the connections between the
drive control unit and the power unit.
Communication errors detected
between the drive control unit and the
power unit.
PU
communication
internal
A5EC
Contact your local ABB representative.
Problem with measurement circuit of
power unit (analog to digital
converter).
Measurement
circuit ADC
A5ED
Contact your local ABB representative.
Problem with current or voltage
measurement of power unit.
Measurement
circuit DFF
A5EE
Contact your local ABB representative.
State feedback from output phases
does not match control signals.
PU state
feedback
A5EF
Informative warning. Wait until
charging finishes before starting the
inverter unit.
Charging in progress.
Charging
feedback
A5F0
Informative warning.
Adequate motor control at requested
output frequency cannot be reached
Switching
frequency
A5F3
574 Fault tracing
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...