
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
10 = 1 s / 1000 = 1 s
Ramp shape at start of deceleration.
0.000 ... 1800.000 s
0.000 s / real32
Defines the shape of the deceleration ramp at the end
of the deceleration. See parameter
Shape time dec 2
23.19
10 = 1 s / 1000 = 1 s
Ramp shape at end of deceleration.
0.000 ... 1800.000 s
60.000 s / real32
Defines the acceleration time for the jogging function
i.e. the time required for the speed to change from zero
to the speed value defined by parameter
See section
.
Acc time jogging
23.20
10 = 1 s / 1000 = 1 s
Acceleration time for jogging.
0.000 ... 1800.000 s
60.000 s / real32
Defines the deceleration time for the jogging function
i.e. the time required for the speed to change from the
speed value defined by parameter
to zero.
See section
.
Dec time jogging
23.21
10 = 1 s / 1000 = 1 s
Deceleration time for jogging.
0.000 ... 1800.000 s
3.000 s / real32
In speed control mode, this parameter defines the
deceleration rate for emergency stop Off3 as the time
it would take for the speed to decrease from the value
of parameter
. This also applies to
torque control because the drive switches to speed
control on receiving an emergency stop Off3 command.
In frequency control mode, this parameter specifies
the time it would take for the frequency to decrease
from the value of
to zero.
The emergency stop mode and activation source are
selected by parameters
and
respectively. Emergency
stop can also be activated through fieldbus.
Note: Emergency stop Off1 uses the standard
deceleration ramp as defined by parameters
(speed and torque control)
Emergency stop
time
23.23
10 = 1 s / 1000 = 1 s
Emergency stop Off3 deceleration time.
0.000 ... 1800.000 s
Inactive / uint32
Selects a source that forces the speed reference to zero
just before it enters the ramp function.
0 = Force speed reference to zero before the ramp
function
1 = Speed reference continues towards the ramp
function as normal
Speed ramp in zero
source
23.24
0
0.
Active
1
1.
Inactive
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
Parameters 273
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...