Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
14
The start and stop commands are taken from the
embedded fieldbus interface.
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
Embedded fieldbus
15
The start and stop commands are taken from another
drive through the master/follower link.
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
M/F link
21
The start and stop commands are taken from the
application program control word (parameter
).
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
Application Program
22
Reserved.
ATF
16
The start and stop commands are taken from an
external (DDCS) controller.
Note: The start signal is always edge-triggered with
this setting regardless of parameter
.
DDCS controller
Edge / uint16
Defines whether the start signal for external control
location EXT2 is edge-triggered or level-triggered.
Note: This parameter is only effective when parameter
is set to
, or
Ext2 start trigger
type
20.7
0
The start signal is edge-triggered.
Edge
1
The start signal is level-triggered.
Level
Not selected / uint32
Selects source 1 for parameter
For the available selections, see parameter
.
Ext2 in1 source
20.8
Not selected / uint32
Selects source 2 for parameter
.
For the available selections, see parameter
.
Ext2 in2 source
20.9
Not selected / uint32
Selects source 3 for parameter
For the available selections, see parameter
.
Ext2 in3 source
20.10
Coast (95.20 b10) /
uint16
Selects the way the motor is stopped when the run
enable signal switches off.
The source of the run enable signal is selected by
parameter
.
Run enable stop
mode
20.11
246 Parameters
Содержание ACS880 N5700 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 position control program N5700 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 32: ...32 ...
Страница 60: ...60 ...
Страница 456: ...Def Type FbEq 16b 32b Description Name Range Selection No 100 1 1 1 Overriding value 0 001 100 000 456 Parameters ...
Страница 546: ...546 ...
Страница 604: ...604 ...
Страница 626: ...626 ...
Страница 640: ...640 ...
Страница 660: ...660 ...