Example: Brake unit with two parallel connected modules
'&
'&
I
I
I
I
I
I
I
I
I
I
9
:
8
9
:
8
Derating
■
Surrounding air temperature derating
In the temperature range +45…55 °C (+113…131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be calculated
by multiplying the current given in the rating table by the derating factor
(k)
:
134 Technical data
Ratings
Definitions
Derating
Ambient temperature derating
In the temperature range +45…55 °C (+113…131 °F), the rated output current is derated
by 0.5 percentage points for every added 1 °C (1.8 °F). The output current can be
calculated by multiplying the current given in the rating table by the derating factor (
k
):
Module type
ACS880-304LC...
No overload use
Light overload
use
Heavy-duty
use
I
1
I
2
I
max
S
n
I
max
P
n
I
Ld
P
Ld
I
Hd
P
Hd
A (AC) A (DC) A (DC)
kVA
A (AC) kW (DC) A (DC)
kW
(DC)
A (DC)
kW
(DC)
U
N
= 690 V
-0820A-7+A019
820
1000
1400
980
1143
932
960
895
800
745
-1540A-7+A019
1540
1880
2632
1840
2149
1752
1805
1682
1504
1401
-2290A-7+A019
2290
2805
3927
2737
3206
2614
2693
2509
2244
2091
-3040A-7+A019
3040
3720
5208
3633
4252
3466
3571
3328
2976
2773
3AXD00000601909.XLS
Nominal ratings
U
N
Nominal input voltage. For
U
1
, see
Electrical power network specification
on page
139
. For
U
2
, see
DC connection data
on page
139
.
I
1
Continuous rms input (AC) current. No overload capability at the coolant temperature of 40 °C
(104 °F) and air temperature of 45 °C (113 °F).
I
2
Continuous rms output (DC) current. No overload capability at the coolant temperature of 40 °C
(104 °F) and air temperature of 45 °C (113 °F).
I
max
Maximum output (DC) current. Available for 10 s at start, otherwise as long as allowed by module
temperature.
S
n
Nominal apparent (AC) power
I
max
Maximum input (AC) current
P
n
Nominal output (DC) power
Light-overload use (50% overload capability) ratings
I
Ld
Continuous current. 50% overload is allowed for one minute every 5 minutes.
P
Ld
Output power in light-overload use
Heavy-duty use (50% overload capability) ratings
I
Hd
Continuous current. 50% overload is allowed for one minute every 5 minutes.
P
Hd
Output power in heavy-duty use
T
1.00
0.95
+45 °C
+113 °F
+55 °C
+131 °F
k
0.90
ACS880-304LC ACS880-104LC_ambient temp derating curve.pdf
■
Coolant temperature derating
See section
■
Antifreeze content derating
See section
Technical data 91
Содержание ACS880-607LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 607LC 3 phase dynamic brake units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 30: ...30 ...
Страница 34: ...34 ...
Страница 46: ...46 ...
Страница 56: ...56 ...
Страница 72: ...7 After the module has drained disconnect the piping from the module 72 Maintenance ...
Страница 88: ...88 ...
Страница 95: ... Bottom entry and exit of cables Dimensions in mm 1 mm 0 0394 in Technical data 95 ...
Страница 96: ...Dimensions in mm 1 mm 0 0394 in 96 Technical data ...
Страница 97: ... Top entry and exit of cables Dimensions in mm 1 mm 0 0394 in Technical data 97 ...
Страница 104: ...Brake unit with bottom exit Dimensions in mm 1 mm 0 0394 in 104 Dimension drawings ...
Страница 105: ...Brake unit with top exit Dimensions in mm 1 mm 0 0394 in Dimension drawings 105 ...
Страница 106: ...Bottom Top Dimensions in mm 1 mm 0 0394 in 106 Dimension drawings ...