Tasks
Starting and checking the cooling system
Fill up and bleed the internal cooling circuit. Start the cooling unit up. See
the internal cooling circuit (page 82)
If the drive is equipped with a cooling unit (ACS880-1007LC): Start up and power up the cooling
unit. See
ACS880-1007LC liquid cooling unit user’s manual
(3AXD50000129607 [English]) and
the delivery-specific circuit diagrams.
Check the cooling system for leaks. Make sure that cooling circuit joints at the shipping split
joining cubicles are tight and that all drain valves have been closed.
Make sure that the coolant can flow freely in all cubicles. Make sure that drive system cools
down. See
ACS880-1007LC liquid cooling unit user’s manual
(3AXD50000129607 [English]).
Install all shrouds (if removed) and close the cabinet doors.
Powering up the DC bus and starting up the inverters
Make sure that all cabinet doors are closed.
Close the disconnector of the supply transformer.
Close the drive auxiliary voltage switch [Q21] to power up the control units.
Start the supply unit. See the procedure in the supply unit hardware manual. When started, the
supply unit charges the capacitors of all inverters and brake units connected to the DC bus.
Start up the inverter units. See the procedure in the inverter unit hardware manual.
Brake units with DC switch/disconnector (F286): Connecting the brake unit to the DC bus
To charge the brake unit capacitors, close the charging switch [Q10].
When the green light on the cabinet door illuminates, close the DC switch/disconnector [Q11]
of the brake unit.
Open the charging switch [Q10].
Note:
The brake unit can start only after the charging switch is open.
Setting up the brake and inverter unit parameters
Check the brake control program parameter settings. See
ACS880 brake control program firm-
ware manual
(3AXD50000020967 [English]).
Operational tests
Test the operation of the braking. See
ACS880 brake control program firmware manual
(3AXD50000020967 [English]).
60 Start-up
Содержание ACS880-607LC
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 607LC 3 phase dynamic brake units Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 30: ...30 ...
Страница 34: ...34 ...
Страница 46: ...46 ...
Страница 56: ...56 ...
Страница 72: ...7 After the module has drained disconnect the piping from the module 72 Maintenance ...
Страница 88: ...88 ...
Страница 95: ... Bottom entry and exit of cables Dimensions in mm 1 mm 0 0394 in Technical data 95 ...
Страница 96: ...Dimensions in mm 1 mm 0 0394 in 96 Technical data ...
Страница 97: ... Top entry and exit of cables Dimensions in mm 1 mm 0 0394 in Technical data 97 ...
Страница 104: ...Brake unit with bottom exit Dimensions in mm 1 mm 0 0394 in 104 Dimension drawings ...
Страница 105: ...Brake unit with top exit Dimensions in mm 1 mm 0 0394 in Dimension drawings 105 ...
Страница 106: ...Bottom Top Dimensions in mm 1 mm 0 0394 in 106 Dimension drawings ...