Typical resistor cable sizes
This table gives copper cable types. Cable sizing is based on max. 9 cables laid on a cable
ladder side by side, three ladder type trays one on top of the other, ambient temperature
30 °C, PVC insulation, surface temperature 70 °C and 90 °C (EN 60204-1 and IEC
60364-5-2/2001). For other conditions, size the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
I
rms dim
is the dimensioning
current.
Cable data
I
rms dim
Frame size
ACS880-604-...
Cable, T=90 °C
Cable, T=70 °C
mm
2
mm
2
A
U
N
= 400 V
3×(3×240+120)
3×(2×(3×120+70))
372
R8i
0500-3
3×(2×(3×150+70))
3×(2×(3×240+120))
559
R8i
0750-3
2×(3×(3×240+120))
2×(3×(2×(3×120+70)))
745
2×R8i
1000-3
2×(3×(2×(3×150+70)))
2×(3×(2×(3×240+120)))
1117
2×R8i
1510-3
3×(3×(2×(3×150+70)))
3×(3×(2×(3×240+120)))
1676
3×R8i
2260-3
4×(3×(2×(3×150+70)))
4×(3×(2×(3×240+120)))
2234
4×R8i
3010-3
5×(3×(2×(3×150+70)))
5×(3×(2×(3×240+120)))
2793
5×R8i
3770-3
U
N
= 500 V
3×(3×240+120)
3×(2×(3×120+70))
372
R8i
0630-5
3×(2×(3×150+70))
3×(2×(3×240+120))
559
R8i
0940-5
2×(3×(3×240+120))
2×(3×(2×(3×120+70)))
745
2×R8i
1260-5
2×(3×(2×(3×150+70)))
2×(3×(2×(3×240+120)))
1117
2×R8i
1880-5
3×(3×(2×(3×150+70)))
3×(3×(2×(3×240+120)))
1676
3×R8i
2830-5
4×(3×(2×(3×150+70)))
4×(3×(2×(3×240+120)))
2234
4×R8i
3770-5
5×(3×(2×(3×150+70)))
5×(3×(2×(3×240+120)))
2793
5×R8i
4710-5
U
N
= 690 V
3×(3×240+120)
3×(2×(3×120+70))
372
R8i
0870-7
3×(2×(3×150+70))
3×(2×(3×240+120))
559
R8i
1300-7
2×(3×(3×240+120))
2×(3×(2×(3×120+70)))
745
2×R8i
1730-7
2×(3×(2×(3×150+70)))
2×(3×(2×(3×240+120)))
1117
2×R8i
2600-7
3×(3×(2×(3×150+70)))
3×(3×(2×(3×240+120)))
1676
3×R8i
3900-7
4×(3×(2×(3×150+70)))
4×(3×(2×(3×240+120)))
2234
4×R8i
5200-7
5×(3×(2×(3×150+70)))
5×(3×(2×(3×240+120)))
2793
5×R8i
6500-7
■
Maximum cable length
The maximum cable length of the resistor cable(s) is 300 m (984 ft). Keep the cable as short
as possible in order to minimize the EMC emissions and stress on chopper IGBTs. The
longer the cable the higher the EMC emissions. The longer the cable the higher the inductive
load and voltage peaks over the IGBT semiconductors of the brake chopper.
Technical data 103
Содержание ACS880-604
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 604 3 phase brake units as modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 10: ...10 ...
Страница 34: ...Overview of kits 34 Cabinet construction ...
Страница 35: ...Stage 1 Installation of common parts Cabinet construction 35 10 ...
Страница 36: ...Stage 2A Installation of DC busbars 1 without DC switch or charging 36 Cabinet construction ...
Страница 37: ...Stage 2B Installation of DC busbars 1 with DC switch and charging Cabinet construction 37 10 ...
Страница 38: ...Stage 3 Installation of quick connector and outgoing resistor busbars cable connection 38 Cabinet construction ...
Страница 39: ...Stage 4 Installation of incoming resistor busbars cable connection Cabinet construction 39 10 ...
Страница 40: ...Stage 5 Installation of mounting plates and cable entries 40 Cabinet construction ...
Страница 41: ...Stage 6 Installation of support plate Cabinet construction 41 10 ...
Страница 42: ...Stage 7 Installation of shrouding 42 Cabinet construction ...
Страница 43: ...Stage 8 Installation of brake chopper module Cabinet construction 43 10 ...
Страница 44: ...44 ...
Страница 48: ...48 ...
Страница 56: ...56 ...
Страница 74: ...74 ...
Страница 76: ...76 ...
Страница 112: ...Frame R8i 112 Dimension drawings ...
Страница 113: ...Dimension drawings 113 ...
Страница 114: ...Control electronics BCU control unit 114 Dimension drawings ...
Страница 123: ...Miscellaneous components Quick connector for frame R8i Dimension drawings 123 ...
Страница 124: ...124 Dimension drawings ...
Страница 125: ... Insertion extraction ramp for frame R8i modules Dimension drawings 125 ...
Страница 126: ...126 Dimension drawings ...
Страница 127: ... CRBB 4 400 188 cooling fan 218 Dimension drawings 127 ...
Страница 128: ...128 Dimension drawings ...