Start-up 115
Connecting voltage to input terminals and auxiliary circuit
Make sure that it is safe to connect voltage. Make sure that:
• nobody is working on the unit or circuits that are wired from outside into the cabinets.
• covers of the motor terminal boxes are on.
Close the circuit breakers supplying the auxiliary circuits [F22], etc.).
Remove any temporary grounding set (if installed).
Close the cabinet doors.
Close the main breaker of the supply transformer.
Close the auxiliary voltage switch [Q21].
Setting the supply unit parameters
Supply modules with C188 (direct-on-line cooling fan):
• Set bit 13 of parameter 195.20 HW options word 1.
If your supply unit consists of one module:
• Check the correct voltage ranges by parameter 195.01 Supply voltage.
• Reboot the control unit by parameter 196.08 Control board boot.
If your supply unit consists of more than one module:
• Set parameter 195.12 accordingly. For the settings, see table on page
. For setting this
parameter, you need a service level pass code. To obtain the pass code, contact your ABB
representative.
• Reboot the control unit by parameter 196.08 Control board boot. Voltage ranges suitable for the
rating IDs selected by parameter 195.12 are shown in parameter 195.01 selections.
• Check the correct voltage ranges by parameter 195.01 Supply voltage.
• Reboot the control unit again by parameter 196.08 Control board boot.
Make sure that the supply unit is in the remote control mode to enable control of the supply unit with
the operating switch [S21]. Use Loc/Rem key of the control panel to change the mode.
Switching the supply unit on
WARNING!
If the drive is equipped with a brake chopper and resistor(s), make sure there
are inverters connected to the intermediate circuit before closing the main contactor. A rule of
thumb: The sum capacitance of the inverters connected must be at least 50% of the sum
capacitance of all inverters.
If there is not enough capacitive load at start, the DC voltage may overshoot the overvoltage limit,
causing immediate start of the brake unit and continuous supply for it by the supply unit. Constant
braking will overload brake choppers and resistors and cause overheating.
If the supply unit is equipped with a main breaker [Q1]:
• Unlock the withdrawn breaker and rack it in.
If the supply unit is equipped with a main switch-disconnector [Q1]:
• Unlock the switch and turn it into the closed position.
Turn the operating switch [S21] to the On position. The DSU receives the Run enable signal and
closes the main contactor [Q2] / main breaker [Q1].
On-load checks
Check that the supply module cooling fan rotates freely in the right direction, that is, sucks air through
the door grating (put a paper sheet on the grating to verify).
Action
Содержание ACS880-304 +A018
Страница 1: ...ABB industrial drives Hardware manual ACS880 304 A018 diode supply modules ...
Страница 4: ......
Страница 14: ...14 ...
Страница 52: ...52 Cabinet construction Kits for 2 D7T 12 pulse Rittal TS 8 ...
Страница 53: ...Cabinet construction 53 Stage 1 Installation of common parts ...
Страница 54: ...54 Cabinet construction Stage 2 Module installation parts ...
Страница 55: ...Cabinet construction 55 Stage 3 Module installation ...
Страница 56: ...56 Cabinet construction Stage 4 AC busbars to the module ...
Страница 57: ...Cabinet construction 57 Stage 5 DC busbars to the module ...
Страница 58: ...58 Cabinet construction Stage 6 Shroud installation ...
Страница 60: ...60 Cabinet construction Kits for 1 D8T 6 pulse Rittal TS 8 ...
Страница 61: ...Cabinet construction 61 Stage 1 Installation of common parts ...
Страница 62: ...62 Cabinet construction Stage 2 Module installation parts ...
Страница 63: ...Cabinet construction 63 Stage 3 Quick connector installation ...
Страница 64: ...64 Cabinet construction Stage 4 DC busbars to the module ...
Страница 65: ...Cabinet construction 65 Stage 5 AC busbars to quick connector ...
Страница 66: ...66 Cabinet construction Stage 6 AC busbar ...
Страница 67: ...Cabinet construction 67 Stage 7 Module installation ...
Страница 68: ...68 Cabinet construction Stage 8 Shroud installation ...
Страница 70: ...70 Cabinet construction Kits for 1 D8T 6 pulse generic cabinet ...
Страница 72: ...72 Cabinet construction Kits for 2 D8T 6 pulse Rittal TS 8 ...
Страница 73: ...Cabinet construction 73 Stage 1 Installation of common parts ...
Страница 74: ...74 Cabinet construction Stage 2 Module installation parts ...
Страница 75: ...Cabinet construction 75 Stage 3 Quick connector installation ...
Страница 76: ...76 Cabinet construction Stage 4 DC busbars ...
Страница 77: ...Cabinet construction 77 Stage 5 AC busbars to quick connector ...
Страница 78: ...78 Cabinet construction Stage 6 AC fuse busbars installation ...
Страница 79: ...Cabinet construction 79 Stage 7 Module installation ...
Страница 80: ...80 Cabinet construction Stage 8 Shroud installation ...
Страница 82: ...82 Cabinet construction Kits for 2 D8T 6 and 12 pulse generic cabinet ...
Страница 84: ...84 Cabinet construction Kits for 2 D8T 12 pulse Rittal TS 8 ...
Страница 85: ...Cabinet construction 85 Stage 1 Installation of common parts ...
Страница 86: ...86 Cabinet construction Stage 2 Module installation parts ...
Страница 87: ...Cabinet construction 87 Stage 3 Quick connectors ...
Страница 88: ...88 Cabinet construction Stage 4 DC busbar installation ...
Страница 89: ...Cabinet construction 89 Stage 5 AC busbars to quick connector ...
Страница 90: ...90 Cabinet construction Stage 6 AC busbars to main AC installation ...
Страница 91: ...Cabinet construction 91 Stage 7 Module installation DC connection flanges ...
Страница 92: ...92 Cabinet construction Stage 8 Shroud installation ...
Страница 94: ...94 Cabinet construction Kits for 3 D8T 6 pulse generic cabinet ...
Страница 104: ...104 Electrical installation 3 b a 5 A cable lead through example This is to be acquired by the cabinet installer ...
Страница 118: ...118 Start up ...
Страница 125: ...Maintenance 125 2 3 ...
Страница 127: ...Maintenance 127 2 3 ...
Страница 132: ...132 Maintenance 4 5 6 7 8 6 10 10 ...
Страница 140: ...140 Maintenance 5 a c b 6 d e 9 ...
Страница 144: ...144 Maintenance 6 b c 7 d 8 ...
Страница 214: ...214 Ordering information ...
Страница 240: ...240 Dimension drawings Dimensions of D7T supply module ...
Страница 241: ...Dimension drawings 241 Dimensions of D8T supply module ...
Страница 242: ...242 Dimension drawings Dimensions of quick connector for D8T module Dimensions in mm 1 mm 0 0394 in ...
Страница 243: ...Dimension drawings 243 Dimensions of the pull out ramp for D8T module Dimensions in mm 1 mm 0 0394 in ...
Страница 244: ...244 Dimension drawings Dimensions of BCU control unit ...
Страница 247: ...Dimension drawings 247 Dimensions of OT2000E12 IEC www abb com Dimensions in mm 1 mm 0 0394 in OT2000E12 ...
Страница 255: ...Dimension drawings 255 Miscellaneous components CRBB 4 400 188 cooling fan 218 Dimensions in mm 1 mm 0 0394 in ...
Страница 256: ...256 Dimension drawings RFI filter and related accessories RFI filter Dimensions in mm 1 mm 0 0394 in ...
Страница 257: ...Dimension drawings 257 Oval toroid kit ...
Страница 258: ...258 Dimension drawings Oval toroid ...
Страница 259: ...Dimension drawings 259 Dimensions of CVAR board UL CSA Dimensions in mm 1 mm 0 0394 in ...
Страница 260: ...260 Dimension drawings ...
Страница 280: ...www abb com drives www abb com drivespartners 3AXD50000010104 Rev C EN 2015 12 03 Contact us ...