138 Start-up
Action
Safety
WARNING!
Obey the safety instructions during the start-up procedure. See chapter
on page
Checks/Settings with no voltage connected
Ensure that the disconnector of the supply transformer is locked to the off (0) position, ie. no voltage
is, and cannot be connected to the drive inadvertently.
Check that the main switch-disconnector [Q1.1] is switched off, or main breaker [Q1] racked out.
Check that the grounding switch [Q9.1] (F259) is switched on.
Check the mechanical and electrical installation of the drive. See
(page
).
Check the settings of breakers/switches in the auxiliary circuits. See the circuit diagrams delivered
with the drive.
Check the tap settings of transformers T21, T101 (if present) and T111 (if present). See
settings of transformers T21, T101 and T111
(page
).
Disconnect any unfinished or uninspected auxiliary voltage (115/230 V AC) cables that lead from the
terminal blocks to the outside of the equipment.
Check that both channels of the Safe torque off circuit connected to the STO inputs of both the supply
control unit [A51] and the inverter control unit [A41] are closed. Refer to the wiring diagrams delivered
with the drive.
If the Safe torque off functionality is used, check that the STO OUT output on the inverter control unit
[A41] is chained to the STO inputs of all inverter modules.
If the Safe torque off functionality is not used, check that the STO input on all inverter modules is
correctly wired to +24 V and ground.
Drives with ground fault monitoring for IT (ungrounded) systems (Q954): Adjust the settings
of the ground fault monitor to suit the installation. See the circuit diagrams of the delivery and
IRDH275B Ground Fault Monitor Operating Manual
by Bender (code: TGH1386en).
Drives with Pt100 relays ((n)L506):
• Check the connections against the circuit diagrams of the delivery.
• Set the alarm and trip levels of the Pt100 relays.
Set the alarm and trip levels of the Pt100 relay as low as possible based on the operating
temperature and test results of the machine. The trip level can be set, for example, 10 °C higher than
what the temperature of the machine is at maximal load in the maximum environmental temperature.
We recommend to set the operating temperatures of the relay, typically for example, as follows:
• 120…140 °C when only tripping is in use
• alarm 120…140 °C and trip 130…150 °C when both alarm and tripping are used.
Powering up the auxiliary circuit of the drive
Make sure that it is safe to connect voltage. Ensure that
• nobody is working on the drive or circuits that have been wired from outside into the drive cabinet
• the cover of the motor terminal box is in place.
Drives with a voltmeter (G334): Make sure that the circuit breaker of the measuring circuit
[F5.1] is closed.
Close the circuit breakers and/or fuse disconnectors supplying the auxiliary voltage circuits.
Close the cabinet doors.
Close the main breaker of the supply transformer.
Содержание ACS880-17
Страница 1: ...ABB industrial drives Hardware manual ACS880 37 drives ...
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 16: ...16 ...
Страница 30: ...30 Introduction to the manual ...
Страница 61: ...Mechanical installation 61 Moving the crate with a forklift Free width for fork tines 750 mm 29 5 ...
Страница 70: ...70 Mechanical installation ...
Страница 105: ...Electrical installation 105 4 5 3 6 7 ...
Страница 107: ...Electrical installation 107 5 6 4 3 ...
Страница 108: ...108 Electrical installation 7 8 8 ...
Страница 109: ...Electrical installation 109 9 10 ...
Страница 111: ...Electrical installation 111 2 360 grounding detail a b b 1 5 a 11 b a PE 10 7 5 6 8 ...
Страница 117: ...Electrical installation 117 PE 11 8 4 9 11 ...
Страница 134: ...134 Control units of the drive ...
Страница 140: ...140 Start up ...
Страница 142: ...142 Fault tracing ...
Страница 154: ...154 Maintenance 4 5 6 7 8 6 10 10 ...
Страница 162: ...162 Maintenance 5 6 3 4 7 ...
Страница 163: ...Maintenance 163 6 8 7 11 10 9 ...
Страница 167: ...Maintenance 167 3 4b 4a 4b 8 ...
Страница 185: ...Technical data 185 Declaration of Conformity ...
Страница 186: ...186 Technical data ...
Страница 196: ...196 Dimensions Dimension drawing examples Frame 1 R8i 1 R8i ...
Страница 197: ...Dimensions 197 Frame 1 R8i 1 R8i top cable entry exit H351 H353 ...
Страница 198: ...198 Dimensions Frame 1 R8i 1 R8i with brake choppers and resistors D150 D151 ...
Страница 199: ...Dimensions 199 Frame 1 R8i 1 R8i with sine output filter E206 ...
Страница 200: ...200 Dimensions Frame 2 R8i 2 R8i eg ACS880 37 1110A 3 IP22 ...
Страница 201: ...Dimensions 201 Frame 2 R8i 2 R8i eg ACS880 37 1210A 3 IP54 ...
Страница 202: ...202 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 1 2 ...
Страница 203: ...Dimensions 203 Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 2 2 ...
Страница 204: ...204 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 1 2 ...
Страница 205: ...Dimensions 205 Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 2 2 ...
Страница 206: ...206 Dimensions Frame 3 R8i 3 R8i 1 2 ...
Страница 207: ...Dimensions 207 Frame 3 R8i 3 R8i 2 2 ...
Страница 208: ...208 Dimensions Frame 3 R8i 3 R8i with common motor terminal cubicle H359 1 2 ...
Страница 209: ...Dimensions 209 Frame 3 R8i 3 R8i with common motor terminal cubicle H359 2 2 ...
Страница 213: ...Dimensions 213 Units with main breaker 600 mm bottom cable entry Units with main breaker 600 mm top cable entry ...
Страница 217: ...Dimensions 217 Sine filter E206 cubicle 1000 mm top cable exit ...
Страница 219: ...Dimensions 219 Cubicle width 300 mm double busbar version bottom cable exit Cubicle width 300 mm top cable exit ...
Страница 220: ...220 Dimensions Cubicle width 300 mm double busbar version top cable exit Cubicle width 400 mm bottom cable exit ...
Страница 221: ...Dimensions 221 Cubicle width 400 mm top cable exit Cubicle width 600 mm bottom cable exit ...
Страница 222: ...222 Dimensions Cubicle width 600 mm top cable exit ...
Страница 234: ...234 The Safe torque off function ...
Страница 244: ...www abb com drives www abb com drivespartners 3AXD50000020437 Rev A EN 2015 02 06 Contact us ...