90 Electrical installation
Motor and motor cable
1. Check that the motor cable is disconnected from the drive output terminals U2, V2 and
W2.
2. Measure the insulation resistance between each phase conductor and the Protective
Earth conductor using a measuring voltage of 1000 V DC. The insulation resistance of
an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the
insulation resistance of other motors, consult the manufacturer’s instructions.
Note
:
Moisture inside the motor casing will reduce the insulation resistance. If moisture is
suspected, dry the motor and repeat the measurement.
Custom brake resistor assembly
See section
(page
Checking the compatibility with IT (ungrounded) systems
EMC E202 is not suitable for use in an IT (ungrounded) system. If the drive is
equipped with E202, disconnect the filter before connecting the drive to the supply
network. For instructions on how to do this, contact your local ABB representative.
WARNING!
If a drive with EMC E202 is installed on an IT system (an
ungrounded power system or a high resistance-grounded [over 30 ohm] power
system), the system will be connected to earth potential through the EMC filter
capacitors of the drive. This may cause danger, or damage the unit.
Attaching the device stickers to the cabinet door
A multilingual device label sticker is delivered with the drive. Attach the stickers in the local
language on the English texts; see section
(page
).
Checking the settings of transformers T21, T101 and T111
Check the tap settings of all auxiliary voltage transformers. Transformer T21 is standard
equipment; T101 and T111 are present if required by the selected options.
The voltage settings of transformers T21 and T101 are made at terminal blocks
T21_X1/X2 and T101_X1/X2 respectively. The settings of transformer T111 are made on
the transformer itself. The locations of the transformers and the terminal blocks are shown
in section
Auxiliary control cubicle (ACU) layout
(page
).
ohm
M
3~
U1
V1
W1PE
Содержание ACS880-17
Страница 1: ...ABB industrial drives Hardware manual ACS880 37 drives ...
Страница 3: ......
Страница 4: ......
Страница 6: ......
Страница 16: ...16 ...
Страница 30: ...30 Introduction to the manual ...
Страница 61: ...Mechanical installation 61 Moving the crate with a forklift Free width for fork tines 750 mm 29 5 ...
Страница 70: ...70 Mechanical installation ...
Страница 105: ...Electrical installation 105 4 5 3 6 7 ...
Страница 107: ...Electrical installation 107 5 6 4 3 ...
Страница 108: ...108 Electrical installation 7 8 8 ...
Страница 109: ...Electrical installation 109 9 10 ...
Страница 111: ...Electrical installation 111 2 360 grounding detail a b b 1 5 a 11 b a PE 10 7 5 6 8 ...
Страница 117: ...Electrical installation 117 PE 11 8 4 9 11 ...
Страница 134: ...134 Control units of the drive ...
Страница 140: ...140 Start up ...
Страница 142: ...142 Fault tracing ...
Страница 154: ...154 Maintenance 4 5 6 7 8 6 10 10 ...
Страница 162: ...162 Maintenance 5 6 3 4 7 ...
Страница 163: ...Maintenance 163 6 8 7 11 10 9 ...
Страница 167: ...Maintenance 167 3 4b 4a 4b 8 ...
Страница 185: ...Technical data 185 Declaration of Conformity ...
Страница 186: ...186 Technical data ...
Страница 196: ...196 Dimensions Dimension drawing examples Frame 1 R8i 1 R8i ...
Страница 197: ...Dimensions 197 Frame 1 R8i 1 R8i top cable entry exit H351 H353 ...
Страница 198: ...198 Dimensions Frame 1 R8i 1 R8i with brake choppers and resistors D150 D151 ...
Страница 199: ...Dimensions 199 Frame 1 R8i 1 R8i with sine output filter E206 ...
Страница 200: ...200 Dimensions Frame 2 R8i 2 R8i eg ACS880 37 1110A 3 IP22 ...
Страница 201: ...Dimensions 201 Frame 2 R8i 2 R8i eg ACS880 37 1210A 3 IP54 ...
Страница 202: ...202 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 1 2 ...
Страница 203: ...Dimensions 203 Frame 2 R8i 2 R8i with main breaker F255 and common motor terminal cubicle H359 2 2 ...
Страница 204: ...204 Dimensions Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 1 2 ...
Страница 205: ...Dimensions 205 Frame 2 R8i 2 R8i with main breaker F255 and top entry top exit H351 H353 2 2 ...
Страница 206: ...206 Dimensions Frame 3 R8i 3 R8i 1 2 ...
Страница 207: ...Dimensions 207 Frame 3 R8i 3 R8i 2 2 ...
Страница 208: ...208 Dimensions Frame 3 R8i 3 R8i with common motor terminal cubicle H359 1 2 ...
Страница 209: ...Dimensions 209 Frame 3 R8i 3 R8i with common motor terminal cubicle H359 2 2 ...
Страница 213: ...Dimensions 213 Units with main breaker 600 mm bottom cable entry Units with main breaker 600 mm top cable entry ...
Страница 217: ...Dimensions 217 Sine filter E206 cubicle 1000 mm top cable exit ...
Страница 219: ...Dimensions 219 Cubicle width 300 mm double busbar version bottom cable exit Cubicle width 300 mm top cable exit ...
Страница 220: ...220 Dimensions Cubicle width 300 mm double busbar version top cable exit Cubicle width 400 mm bottom cable exit ...
Страница 221: ...Dimensions 221 Cubicle width 400 mm top cable exit Cubicle width 600 mm bottom cable exit ...
Страница 222: ...222 Dimensions Cubicle width 600 mm top cable exit ...
Страница 234: ...234 The Safe torque off function ...
Страница 244: ...www abb com drives www abb com drivespartners 3AXD50000020437 Rev A EN 2015 02 06 Contact us ...