Make sure that the drive is compatible with the grounding
system
The standard drive with ground-to-phase varistors connected can be installed to a
symmetrically grounded TN-S system. If you install the drive to another system, you
may need to disconnect the EMC filter and ground-to-phase varistors. See
.
■
EMC filter oE200 and +E202
Do not install the drive with EMC E200 or E202 connected to a
system that the filter is not suitable for. This can cause danger, or damage the
drive.
Note: When EMC E200 or +E202 is disconnected, the drive EMC compatibility
is considerably reduced.
■
Ground-to-phase varistor
A drive with the ground-to-phase varistor connected can be installed to a symmetrically
grounded TN-S system. If you install the drive to another system, you may need to
disconnect the varistor. See
ACS880 frames R1 to R11 EMC filter and ground-to-phase
varistor disconnecting instructions (3AUA0000125152 [English])
Do not install the drive with the ground-to-phase varistor connected to a system
that the varistor is not suitable for. If you do, the varistor circuit can be
damaged.
Move the drive to the installation site and unpack it
Move the transport package by pallet truck to the installation site.
To unpack the package:
•
Cut the straps.
•
Lift the lid.
•
Lift the sleeve.
•
Unpack the top boxes.
•
Insert lifting hooks to the drive and LCL filter module lifting lugs (see section
) and lift the modules to the
installation place.
EN – Quick installation and start-up guide 7