Protecting the motor against thermal overload
According to regulations, the motor must be protected against thermal overload and the
current must be switched off when overload is detected. The drive includes a motor thermal
protection function that protects the motor and switches off the current when necessary.
Depending on a drive parameter value, the function either monitors a calculated temperature
value (based on a motor thermal model) or an actual temperature indication given by motor
temperature sensors. The user can tune the thermal model further by feeding in additional
motor and load data.
The most common temperature sensors are:
•
motor sizes IEC180…225: thermal switch, eg. Klixon
•
motor sizes IEC200…250 and larger: PTC or Pt100.
See the firmware manual for more information on the motor thermal protection, and the
connection and use of the temperature sensors.
Protecting the drive against ground faults
The drive is equipped with an internal ground fault protective function to protect the unit
against ground faults in the motor and motor cable in TN (grounded) networks. This is not
a personnel safety or a fire protection feature. The ground fault protective function can be
disabled with a parameter, refer to the firmware manual.
An optional ground fault monitoring device (+Q954) is available for IT (ungrounded) systems.
The option includes a ground fault indicator on the drive cabinet door.
■
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
Note:
The drive contains capacitors connected between the main circuit and the frame. These
capacitors and long motor cables increase the ground leakage current and may cause fault
current circuit breakers to function.
Implementing the emergency stop function
You can order the drive with a category 0 or category 1 emergency stop function.
For safety reasons, install the emergency stop devices at each operator control station and
at other operating stations where emergency stop may be needed.
Note:
Pressing the stop key
on the control panel of the drive, or turning the operating switch
of the drive from position “1” to “0” does not generate an emergency stop of the motor or
separate the drive from dangerous potential.
See the appropriate emergency stop user’s manual for the wiring, start-up and operation
instructions.
Manual code
(English)
User’s manual
Option code
Emergency stop, stop category 0 (using main contactor/breaker)
+Q951
Emergency stop, stop category 0 (using main contactor/breaker) with
push button monitoring
+Q951+Q984
Guidelines for planning the electrical installation 77
Содержание ACS880-07CLC
Страница 1: ...ABB industrial drives Hardware manual ACS880 07CLC drives ...
Страница 2: ......
Страница 4: ......
Страница 64: ...64 ...
Страница 82: ...82 ...
Страница 91: ...PE PE 10 13 12 22 Electrical installation 91 ...
Страница 122: ...122 ...
Страница 124: ...124 ...
Страница 132: ...5 4 11 7 6 8 132 Maintenance ...
Страница 133: ...14 15 16 12 13 17 Maintenance 133 ...
Страница 141: ...5 Set the real time clock Maintenance 141 ...
Страница 142: ...142 ...
Страница 150: ...150 ...
Страница 176: ...ACS880 07CLC 0390A 7 C121 marine construction 176 Dimensions ...
Страница 177: ...ACS880 07CLC 1310A 7 Dimensions 177 ...
Страница 178: ...ACS880 07CLC 2180A 7 C121 marine construction 178 Dimensions ...
Страница 179: ...ACS880 07CLC 3260A 7 C121 marine construction Dimensions 179 ...
Страница 181: ... 2 D8D Dimensions 181 ...
Страница 182: ... 3 D8D 182 Dimensions ...
Страница 183: ... 4 D8D Dimensions 183 ...
Страница 185: ...Inverter module cubicle with two R8i modules bottom cable exit Dimensions 185 ...
Страница 186: ...Inverter module cubicle with three R8i modules bottom cable exit 186 Dimensions ...
Страница 187: ...Brake chopper cubicle D150 Dimensions 187 ...
Страница 188: ...188 ...
Страница 202: ...202 ...
Страница 211: ......
Страница 212: ......
Страница 214: ...Contact us www abb com drives 3AXD50000131457 Rev A EN EFFECTIVE 2018 03 09 3AXD50000131457A ...