Terminal and entry data for the power cables
The maximum accepted cable size is 4×(3×240) mm
2
or 4×(3×500 MCM). Screw size
for connecting busbars to the drive module input and output busbars: M12, tightening
torque 50…75 N·m (37…55 lbf·ft).
■
Units without full-size output cable connection terminals and with a
common mode filter (+E208)
It is possible to use the maximum cable size (4×[3×240] mm
2
or 4×[3×500 MCM]) only
with special cable lugs and additional insulation. For more information, contact your
local ABB representative.
Terminal data for the control cables
See section
Default I/O diagram of the drive control unit (ZCU-1x) (page 103)
Electrical power network specification
ACS880-04F-xxxx-3 drives: 380…415 VAC 3-phase +10%…-15%. This is indic-
ated in the type designation label as typical input voltage level 3~400 V AC.
Voltage (
U
1
)
ACS880-04F-xxxx-5 drives: 380…500 V AC 3-phase +10%…-15%. This is indic-
ated in the type designation label as typical input voltage levels
3~400/480/500 V AC.
ACS880-04F-xxxx-7 drives: 525…690 V AC 3-phase +10%…-15%. This is indic-
ated in the type designation label as typical input voltage levels
3~525/600/690 V AC.
TN (grounded) and IT (ungrounded) systems
Network type
Maximum allowable prospective short-circuit current is 65 kA when protected
by the fuses given in the fuse table.
Rated conditional short-
circuit current I
cc
(IEC 61439-1)
The drive is suitable for use on a circuit capable of delivering not more than
100 kA rms symmetrical amperes at 600 V maximum when protected by the
fuses given in the fuse table.
Short-circuit current
protection (UL 61800-5-
1, CSA C22.2 No. 274-17)
50/60 Hz. Variation ±5% of nominal frequency.
Frequency (
f
1
)
Max. ± 3% of nominal phase to phase input voltage
Imbalance
0.98 (at nominal load)
Fundamental power
factor (cos phi
1
)
Motor connection data
Asynchronous AC induction motors, permanent magnet motors and AC induc-
tion servomotors.
Motor types
This is indicated in the type designation label as typical output voltage level
3~0…
U
1
.
Voltage (
U
2
)
0…500 Hz
Frequency (
f
2
)
For drives with d
u/dt filter: 200 Hz
For drives with sine filter: 120 Hz
0.01 Hz
Frequency resolution
146 Technical data
Содержание ACS880-04F-504A-3
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 36: ...36 ...
Страница 44: ...44 ...
Страница 50: ...50 Mechanical installation ...
Страница 56: ...56 ...
Страница 116: ...116 ...
Страница 122: ...4 3 2 122 Maintenance ...
Страница 128: ...128 ...
Страница 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Страница 158: ...158 ...
Страница 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Страница 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Страница 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Страница 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Страница 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Страница 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Страница 166: ...3AXD50000038119 166 Dimension drawings ...
Страница 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Страница 168: ...168 ...