The following temperature profile is used in safety value calculations:
•
670 on/off cycles per year with Δ
T = 71.66 °C
•
1340 on/off cycles per year with Δ
T = 61.66 °C
•
30 on/off cycles per year with Δ
T = 10.0 °C
•
32 °C board temperature at 2.0% of time
•
60 °C board temperature at 1.5% of time
•
85 °C board temperature at 2.3% of time.
•
The STO is a type B safety component as defined in IEC 61508-2.
•
Relevant failure modes:
•
The STO trips spuriously (safe failure)
•
The STO does not activate when requested
•
A fault exclusion on the failure mode “short circuit on printed circuit board”
has been made (EN 13849-2, table D.5). The analysis is based on an assumption
that one failure occurs at one time. No accumulated failures have been
analyzed.
•
STO response times:
•
STO reaction time (shortest detectable break): 1 ms
•
STO response time: 2 ms (typical), 30 ms (maximum)
•
Fault detection time: Channels in different states for longer than 200 ms
•
Fault reaction time: Fault detection time + 10 ms.
•
Indication delays:
•
STO fault indication (parameter 31.22) delay: < 500 ms
•
STO warning indication (parameter 31.22) delay: < 1000 ms.
■
Terms and abbreviations
Description
Reference
Term or
abbreviation
Classification of the safety-related parts of a control system in
respect of their resistance to faults and their subsequent behavior
in the fault condition, and which is achieved by the structural
arrangement of the parts, fault detection and/or by their
reliability. The categories are: B, 1, 2, 3 and 4.
EN ISO 13849-1
Cat.
Common cause failure (%)
EN ISO 13849-1
CCF
Diagnostic coverage (%)
EN ISO 13849-1
DC
Hardware fault tolerance
IEC 61508
HFT
Mean time to dangerous failure: (Total number of life units) /
(Number of dangerous, undetected failures) during a particular
measurement interval under stated conditions
EN ISO 13849-1
MTTF
D
Average probability of dangerous failure on demand, that is, mean
unavailability of a safety-related system to perform the specified
safety function when a demand occurs
IEC 61508
PFD
avg
Average frequency of dangerous failures per hour, that is, average
frequency of a dangerous failure of a safety related system to
perform the specified safety function over a given period of time
IEC 61508
PFH
Average frequency of dangerous failures per hour for the
diagnostic function of STO
IEC/EN 62061
PFH
diag
Performance level. Levels a…e correspond to SIL
EN ISO 13849-1
PL
Periodic test performed to detect failures in a safety-related
system so that, if necessary, a repair can restore the system to
an "as new" condition or as close as practical to this condition
IEC 61508, IEC 62061
Proof test
The Safe torque off function 187
Содержание ACS880-04F-504A-3
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 04F drive modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 26: ...26 ...
Страница 36: ...36 ...
Страница 44: ...44 ...
Страница 50: ...50 Mechanical installation ...
Страница 56: ...56 ...
Страница 116: ...116 ...
Страница 122: ...4 3 2 122 Maintenance ...
Страница 128: ...128 ...
Страница 143: ... Package dimensions Package dimensions without IP shroud kit Technical data 143 ...
Страница 158: ...158 ...
Страница 160: ...Standard configuration IP20 UL Type Open 160 Dimension drawings ...
Страница 161: ...Drive module with options E208 and H370 IP20 UL Type Open Dimension drawings 161 ...
Страница 162: ...Drive module with options 0B051 E208 0H371 IP00 UL Type Open 162 Dimension drawings ...
Страница 163: ...Drive module with options 0B051 E208 0H371 C217 IP00 UL Type Open Dimension drawings 163 ...
Страница 164: ...Drive module with options 0B051 0H371 IP00 UL Type Open 164 Dimension drawings ...
Страница 165: ...Mounting plate opening 3AXD50000038119 Dimension drawings 165 ...
Страница 166: ...3AXD50000038119 166 Dimension drawings ...
Страница 167: ...External control unit 3AXD50000011687 Dimension drawings 167 ...
Страница 168: ...168 ...