226 Parameters
Defines the motor load curve together with parameters
The load curve is
used by the motor thermal protection model to estimate the
motor temperature.
When the parameter is set to 100%, the maximum load is
taken as the value of parameter
(higher loads heat up the motor). The load curve level should
be adjusted if the ambient temperature differs from the
nominal value set in
100%
50 … 150%
Maximum load for the motor load curve.
1 = 1%
Defines the motor load curve together with parameters
and
. Defines the
maximum motor load at zero speed of the load curve. A higher
value can be used if the motor has an external motor fan to
boost the cooling. See the motor manufacturer's
recommendations.
See parameter
.
70%
25…150%
Zero speed load for the motor load curve.
1 = 1%
Defines the motor load curve together with parameters
and
. Defines the
break point frequency of the load curve i.e. the point at which
the motor load curve begins to decrease from the value of
parameter
towards the value of
parameter
See parameter
.
45.00 Hz
1.00 … 100.00 Hz
Break point for the motor load curve.
See par.
No.
Name/Value
Description
Def
/
FbEq16
50
100
150
I/I
N
(%)
I
= Motor current
I
N
= Nominal motor current
Drive output
frequency
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...