Parameters 225
Defines the warning limit for temperature monitoring function
2. When measured temperature 2 exceeds the limit, a warning
(
) is generated.
Note:
With a PTC sensor, the unit is ohms.
110 °C,
4000 ohm
-60 … 1000 °C,
0…5000 ohm
Warning limit for temperature monitoring function 2.
1 = 1 unit
Selects the input for parameter
,
.
Not selected
None.
0
AI1 actual value
Analog input AI1 on the control unit.
1
AI2 actual value
Analog input AI2 on the control unit.
2
Source selection (see
on page
).
-
0000 0000b …
0011 1111b
FPTC-xx module configuration word.
1 = 1
Defines the ambient temperature of the motor for the motor
thermal protection model.
The motor thermal protection model estimates the motor
temperature on the basis of parameters
. The
motor temperature increases if it operates in the region above
the load curve, and decreases if it operates in the region
below the load curve.
WARNING!
The model cannot protect the motor if the
motor does not cool properly because of dust, dirt, etc.
20 °C
-60 … 100 °C
Ambient temperature.
1 = 1°
No.
Name/Value
Description
Def
/
FbEq16
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...