204 Parameters
Selects which indications are given when one or both Drive
interlock (DIL) signals are switched off or lost. The indications
also depend on whether the drive is running or stopped when
this occurs.
The tables at each selection below show the indications
generated with that particular setting.
Notes:
• This parameter does not affect the operation of the DIL
function itself. The DIL function will operate regardless of
the setting of this parameter: a running drive will stop upon
removal of one or both DIL signals, and will not start until
both DIL signals are restored and all faults reset.
• The loss of only one DIL signal always generates a fault as
it is interpreted as a malfunction.
• This parameter cannot be changed while the drive is
running.
For more information on the DIL, see the
Hardware manual
of
the drive.
Fault/Fault
0
Fault/Warning
1
No.
Name/Value
Description
Def
/
FbEq16
Inputs
Indication (running or stopped)
IN1
IN2
0
0
Fault
0
1
Faults
and
1
0
Faults
and
1
1
(Normal operation)
Inputs
Indication
IN1
IN2
Running
Stopped
0
0
Fault
Warning
0
1
Warning
1
0
Warning
1
1
(Normal operation)
Содержание ACS860
Страница 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 54: ...54 Program features ...
Страница 78: ...78 Program features ...
Страница 90: ...90 Application macros ...
Страница 342: ...342 Additional parameter data ...
Страница 380: ...380 Fault tracing ...
Страница 381: ...Fault tracing 381 ...
Страница 382: ...382 Fault tracing ...
Страница 436: ...436 Control chain diagrams ...