10 Quick Start-up Guide for ACS850 with Standard Control Program
• maximum torque
For the Normal ID run (see below), this value should
be at least 100% of motor nominal torque defined
earlier.
20.07
Maximum torque1
• minimum torque
20.08
Minimum torque1
The question “Do you want to perform id-run now?” is displayed. The ID run
(identification run) will identify the characteristics of the motor for optimum control.
If you do not wish to perform the ID run at this point, select
No
to complete the Motor
Set-up firmware assistant. Proceed to section
3 – Start/Stop configuration
.
If you wish to perform the ID run, continue with the following steps BEFORE selecting
Yes
.
WARNING!
With Normal or Reduced ID run the motor will run at up to
approximately 50…100% of the nominal speed during the ID run. ENSURE
THAT IT IS SAFE TO RUN THE MOTOR BEFORE PERFORMING THE ID
RUN!
Check the direction of rotation of the motor. During
the run (Normal or Reduced), the motor will rotate in
the forward direction.
Ensure the Safe Torque Off and emergency stop
circuits (if present) are closed.
Select
Yes
and press OK.
Select the ID run method.
The ID run will be performed at the next start of the
drive.
99.13
Idrun mode
NORMAL ID
run should be selected whenever
possible.
Note:
The driven machinery must be de-coupled
from the motor with Normal ID run:
• if the load torque is higher than 20%, or
• if the machinery is not able to withstand the
nominal torque transient during the ID run.
The
REDUCED ID
run should be selected instead of
the Normal ID run if the mechanical losses are
higher than 20%, i.e. the motor cannot be
de-coupled from the driven equipment, or full flux is
required to keep the motor brake open (conical
motor).
Forward
When drive output phases U2,
V2 and W2 are connected to the
corresponding motor terminals:
Reverse
Содержание ACS850 series
Страница 46: ...46 Kurzanleitung f r die Inbetriebnahme des ACS850 mit Standard Regelungsprogramm...
Страница 76: ...76 Guide de mise en route de l ACS850 avec le programme de commande Standard...
Страница 106: ...106 Beknopte opstartgids voor de ACS850 met standaard besturingsprogramma...
Страница 163: ...ACS850 163 ACS850 ACS850 ACS850 ACS850 3AUA0000054544...
Страница 164: ...164 ACS850 20 5E Output 2021 LOC 00 A 00 0 0 0 0 REM 0 00rpm LOC REM 00 A 00 0 0 0 0 LOC 0 00rpm...
Страница 165: ...ACS850 165 MENU 16 15 1 C TRUE 0 C FALSE Const 1 LOC...
Страница 167: ...ACS850 167 1 OK 9901 Deutsch 0407 hex LOC 1 LOC LOC...
Страница 168: ...168 ACS850 Factory Hand Auto PID control Torque control Sequential control OK OK 2 OK 1 LOC LOC...
Страница 169: ...ACS850 169 99 04 DTC 1 6 99 05...
Страница 172: ...172 ACS850 0 20 02 20 05 100 20 07 1 20 08 1 Do you want to perform id run now 3 50 100 OK U2 V2 W2...
Страница 173: ...ACS850 173 99 13 NORMAL ID 20 REDUCED ID 20 STANDSTILL ID...
Страница 174: ...174 ACS850 20 99 05 ID ID OK 3 OK 1 EXT1 10 01 10 02 10 03 10 01 1 10 02 0 1 10 01 1 10 02 1 1 10 03 2 1 1 LOC LOC...
Страница 176: ...176 ACS850 1 10 11 OFF3 22 12 10 13 3 OK 4 OK EXT1 EXT2 Min Max 12 03 1 12 05 2 1 LOC LOC...
Страница 180: ...180 ACS850...
Страница 181: ...ACS850 181 ACS850 ACS850 ACS850 ACS850 3AUA0000045497...
Страница 188: ...188 ACS850 100 20 07 Maximum torque1 20 08 Minimum torque1 No 3 Yes 50 100 Yes OK 99 13 Idrun mode 20 20 U2 V2 W2...
Страница 195: ......
Страница 196: ...3AUA0000045498 REV D MUL EFFECTIVE 2012 08 06...