Technical data
124
Symbols
Note:
The ratings apply at an ambient temperature of 40 °C (104 °F). At lower temperatures the ratings
are higher.
Sizing
See page
115
.
Derating
See page
115
.
Fuses
For branch circuit protection per NEC, the drive is equipped with UL class T or L
fuses listed below. Fast acting class T/L or faster fuses are recommended in the
USA.
Check from the fuse time-current curve that the operating time of the fuse is
below 0.1 seconds
. The operating time depends on the supply network impedance
and the cross-sectional area and length of the supply cable. The short-circuit current
can be calculated as shown in section
Fuses
on page
116
.
Note 1:
See also
Planning the electrical installation
:
Thermal overload and short-circuit protection
.
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3:
Larger fuses than the recommended ones must not be used.
Note 4:
Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
Note 5:
Circuit breakers must not be used without fuses.
I
max
maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Normal use
(10% overload capability)
I
2N
continuous rms current. 10% overload is typically allowed for one minute every 5 minutes.
P
N
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (460 V or
575 V).
Heavy-duty use
(50% overload capability)
I
2hd
continuous rms current. 50% overload is typically allowed for one minute every 5 minutes.
P
hd
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (460 V or
575 V).
Содержание ACS800-U7
Страница 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Страница 4: ......
Страница 28: ...Operation principle and hardware description 28 ...
Страница 51: ...Planning the electrical installation 51 ...
Страница 60: ...Planning the electrical installation 60 ...
Страница 76: ...Electrical installation 76 ...
Страница 84: ...Motor control and I O board RMIO 84 ...
Страница 112: ...Maintenance 112 ...
Страница 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Страница 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Страница 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Страница 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...