Technical data
98
US tables
NEMA ratings
The NEMA ratings for the ACS800-U11 and ACS800-11 with 60 Hz supplies are
given below. The symbols are described below the table. For sizing, derating and
50 Hz supplies, see
*
allowed with motor power < 125 HP and a reactive power reference of 0
**
allowed with motor power < 50 HP and a reactive power reference of 0
Symbols
Note 1:
The ratings apply at an ambient temperature of 40 °C (104 °F). In lower temperatures the
ratings are higher (except
I
max
).
ACS800-U11 size
ACS800-11 size
I
max
Normal use
Heavy-duty use
Frame
size
Air flow
Heat
dissipation
A
I
2N
A
P
N
HP
I
2hd
A
P
hd
HP
ft
3
/min
BTU/Hr
Three-phase supply voltage 208 V, 220 V,
230 V
or 240 V
-0011-2
52
32
10
26
7.5
R5
206
1730
-0016-2
68
45
15
38
10
R5
206
2380
-0020-2
90
56
20
45
10
R5
206
3110
-0025-2
118
69
25
59
15
R5
206
3760
-0030-2
144
83
30
72
20
R5
206
4500
-0040-2
168
114
40
84
25
R6
238
5420
-0050-2
234
143
50
117
30
R6
238
7260
-0060-2
264
157
60
132
40
R6
238
8650
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V,
460
V or 480 V
-0020-5
52
29
20
25
15
R5
206
2240
-0025-5
61
34
25
30
20
R5
206
2600
-0030-5
68
45
30
37
25
R5
206
3420
-0040-5
90
55
40
47
30
R5
206
4140
-0050-5
118
67
50
57
40
R5
206
4960
-0060-5
144
78
60
65**
50
R5
206
5980
-0070-5
168
114
75
88
60
R6
238
8030
-0100-5
234
132
100
114
75
R6
238
9570
-0120-5
264
156*
125
125
100
R6
238
11620
PDM code: 00317419-C
Nominal ratings
I
max
maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
temperature.
Normal use
(10 % overload capability)
I
2N
continuous rms current. 10 % overload is typically allowed for one minute every 5 minutes.
P
N
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V or
460 V).
Heavy-duty use
(50 % overload capability)
I
2hd
continuous rms current. 50 % overload is typically allowed for one minute every 5 minutes.
P
hd
typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V or
460 V).
Содержание ACS800-11
Страница 1: ...ACS800 Hardware Manual ACS800 11 Drives 5 5 to 110 kW ACS800 U11 Drives 7 5 to 125 HP ...
Страница 4: ......
Страница 12: ...Safety instructions 12 ...
Страница 30: ...The ACS800 11 U11 30 ...
Страница 36: ...Mechanical installation 36 ...
Страница 54: ...Planning the electrical installation 54 ...
Страница 59: ...Electrical installation 59 1 2 3 Views of frame size R5 U1 V1 W1 V2 W2 U2 UDC UDC 5 5 PE 6 6 8 9 9 ...
Страница 74: ...Installation checklist 74 ...
Страница 84: ...Operation 84 ...
Страница 104: ...Technical data 102 ...
Страница 105: ...Dimensional drawings 103 Dimensional drawings The dimensions are given in millimetres and inches ...
Страница 108: ...Dimensional drawings 106 ...
Страница 111: ...External 24 V power supply for the RMIO board 109 5 6 7 8 ...
Страница 112: ...External 24 V power supply for the RMIO board 110 ...
Страница 113: ......