30 Start-up, control with I/O and ID run
Pre-check
WARNING!
The motor will run at up to approximately 50…80% of the nominal
speed during the ID run. The motor will rotate in the forward direction.
Make
sure that it is safe to run the motor before performing the ID run!
De-couple the motor from the driven equipment
Check that the values of the motor data parameters are equivalent to those on the motor
nameplate.
Check that the STO circuit is closed.
If parameter values (from group
) are changed
before the ID run, check that the new settings meet the following conditions:
< 0 rpm
= motor rated speed (Normal ID run procedure needs the motor to
be run at 100% speed.)
>
I
HD
> 50% or
> 50%, depending on which
torque limit set is in use according to parameter
Check that signals
) is active
start enable (parameter
) is active
) is active.
Make sure that the panel is in local control (text Local shown at the top left). Press key
to switch between local and remote control.
ID run
Go to the
Main
menu by pressing
(
Menu
)
in the Home view.
Press .
Loc/Rem
ACS580 FW.book Page 30 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...