Parameters 299
Defines the “at setpoint” limits for frequency control of the
drive. When the absolute difference between reference
(
) and actual frequency (
) is smaller than
, the drive is considered to be “at setpoint”. This is
indicated by bit 8 of
2.00 Hz
0.00…1000.00 Hz
Limit for “at setpoint” indication in frequency control.
See par.
Defines the “at setpoint” limits for torque control of the drive.
When the absolute difference between reference (
) and actual torque (
, the drive is
considered to be “at setpoint”. This is indicated by bit 8 of
5.0%
0.0…300.0%
Limit for “at setpoint” indication in torque control.
See par.
Defines the trigger level for “above limit” indication in speed
control. When actual speed exceeds the limit, bit 10 of
is set.
1500.00 rpm
0.00…30000.00
rpm
“Above limit” indication trigger level for speed control.
See par.
Defines the trigger level for “above limit” indication in
frequency control. When actual frequency exceeds the limit,
bit 10 of
is set.
50.00 Hz
0.00…1000.00 Hz
“Above limit” indication trigger level for frequency control.
See par.
No.
Name/Value
Description
Def/FbEq16
(Hz)
0 Hz
(Hz)
(Hz)
(Hz)
Drive at setpoint
(
bit 8 = 1)
(%)
0%
Drive at setpoint
(
bit 8 = 1)
ACS580 FW.book Page 299 Wednesday, September 21, 2016 9:48 PM
Содержание ACS580 Series
Страница 88: ...84 ACS580 FW book Page 84 Wednesday September 21 2016 9 48 PM ...
Страница 146: ...142 Program features ACS580 FW book Page 142 Wednesday September 21 2016 9 48 PM ...
Страница 444: ...440 Fieldbus control through a fieldbus adapter ACS580 FW book Page 440 Wednesday September 21 2016 9 48 PM ...
Страница 461: ...ACS580 FW book Page 457 Wednesday September 21 2016 9 48 PM ...
Страница 462: ...3AXD0000016097 Rev D EN 2016 09 02 ACS580 FW book Page 458 Wednesday September 21 2016 9 48 PM ...