To comply with the EMC requirements of the CE mark, use one of the preferred cable types.
See
Preferred power cable types (page 71)
Symmetrical shielded cable reduces electromagnetic emission of the whole drive system
as well as the stress on motor insulation, bearing currents and wear.
Metal conduit reduces electromagnetic emission of the whole drive system.
The protective conductor must always have an adequate conductivity.
Unless local wiring regulations state otherwise, the cross-sectional area of the protective
conductor must agree with the conditions that require automatic disconnection of the supply
required in 411.3.2. of IEC 60364-4-41:2005 and be capable of withstanding the prospective
fault current during the disconnection time of the protective device. The cross-sectional area
of the protective conductor can either be selected from the table below or calculated according
to 543.1 of IEC 60364-5-54.
This table shows the minimum cross-sectional area of the protective conductor related to
the phase conductor size according to IEC 61800-5-1 when the phase conductor and the
protective conductor are made of the same metal. If this is not so, the cross-sectional area
of the protective earthing conductor shall be determined in a manner which produces a
conductance equivalent to that which results from the application of this table.
Minimum cross-sectional area of the corresponding
protective conductor
S
p
(mm
2
)
Cross-sectional area of the phase conductors
S (mm
2
)
S
1)
,
2)
S ≤ 16
16
16 < S ≤ 35
S/2
35 < S
1) Drive safety standard IEC/EN 61800-5-1:
• use a protective earth conductor with a cross-section of at least 10 mm
2
(8 AWG) Cu or 16 mm
2
(6 AWG) Al, or
• use a second protective earth conductor of the same cross-sectional area as the original protective earthing conductor,
or
• use a device which automatically disconnects the supply if the protective earth conductor breaks.
2) Drive safety standard IEC/EN 61800-5-1: If the protective earth conductor is separate (ie, it does not form part of the input
power cable or the input power cable enclosure), the cross section must be at least:
• 2.5 mm
2
(14 AWG) when the conductor is mechanically protected, or
• 4 mm
2
(12 AWG) when the conductor is not mechanically protected.
■
Typical power cable sizes
See the technical data of the drive (or unit).
70 Guidelines for planning the electrical installation
Содержание ACS580-07
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS580 07 Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 14: ...14 ...
Страница 21: ...Measuring points of frames R6 to R9 are shown below PE L1 L2 L3 Safety instructions 21 ...
Страница 26: ...26 ...
Страница 30: ...30 ...
Страница 50: ...50 ...
Страница 62: ...62 ...
Страница 95: ...Electrical installation 95 11 ...
Страница 101: ...Electrical installation 101 11 ...
Страница 114: ...114 ...
Страница 124: ...Note Only 24 V DC can be used for STO Only PNP input configuration can be used 124 Control unit ...
Страница 128: ...128 ...
Страница 134: ...134 ...
Страница 142: ...142 Maintenance ...
Страница 155: ...3 4 5 Maintenance 155 ...
Страница 157: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 157 ...
Страница 161: ...4 5 3 Maintenance 161 ...
Страница 163: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 163 ...
Страница 169: ...1 2 3 5a 5b CR2032 Maintenance 169 ...
Страница 170: ...170 ...
Страница 185: ...Frame R6 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 185 ...
Страница 186: ...Frame R6 Input and motor cable terminal dimensions option F289 DET A 186 Technical data ...
Страница 190: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS250 DET A 190 Technical data ...
Страница 191: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 191 ...
Страница 192: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit option F289 192 Technical data ...
Страница 193: ...Frames R6 and R7 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 193 ...
Страница 196: ...Frame R8 Input and motor cable terminal dimensions bottom entry and exit option F289 196 Technical data ...
Страница 199: ...Frames R8 and R9 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 199 ...
Страница 201: ...Frame R9 Input and motor cable terminal dimensions option F289 Technical data 201 ...
Страница 202: ...Frame R10 Input and motor cable terminal dimensions bottom entry and exit 202 Technical data ...
Страница 203: ...Frame R10 Input and motor cable terminal dimensions bottom entry and exit option E205 Technical data 203 ...
Страница 204: ...Frame R10 Input and motor cable terminal dimensions top entry and exit 204 Technical data ...
Страница 205: ...Frame R10 Input and motor cable terminal dimensions top entry and exit option F289 Technical data 205 ...
Страница 206: ...Frame R11 Input and motor cable terminal dimensions bottom entry and exit 206 Technical data ...
Страница 207: ...Frame R11 Input and motor cable terminal dimensions bottom entry and exit option E205 Technical data 207 ...
Страница 208: ...Frame R11 Input and motor cable terminal dimensions top entry and exit 208 Technical data ...
Страница 209: ...Frame R11 Input and motor cable terminal dimensions top entry and exit option F289 Technical data 209 ...
Страница 217: ...Declaration of Conformity Technical data 217 ...
Страница 218: ...218 Technical data ...
Страница 223: ...Dimension drawings Example dimension drawings are shown below 13 Dimension drawings 223 ...
Страница 224: ...Frames R6 and R7 IP21 UL Type 1 224 Dimension drawings ...
Страница 225: ...Frames R6 and R7 B054 IP42 UL Type 1 Dimension drawings 225 ...
Страница 226: ...Frames R6 and R7 B055 IP54 UL Type 12 226 Dimension drawings ...
Страница 227: ...Frames R6 and R7 H351 and H353 top entry and exit Dimension drawings 227 ...
Страница 228: ...Frames R6 and R7 F289 228 Dimension drawings ...
Страница 229: ...Frames R6 and R7 F289 H351 H353 Dimension drawings 229 ...
Страница 230: ...Frames R8 and R9 IP21 230 Dimension drawings ...
Страница 231: ...Frames R8 and R9 B054 IP42 UL Type 1 Dimension drawings 231 ...
Страница 232: ...Frames R8 and R9 B055 IP54 UL Type 12 232 Dimension drawings ...
Страница 233: ...Frames R8 and R9 H351 and H353 top entry and exit Dimension drawings 233 ...
Страница 234: ...Frames R8 and R9 F289 234 Dimension drawings ...
Страница 235: ...Frames R8 and R9 F289 H351 H353 Dimension drawings 235 ...
Страница 236: ...Frames R10 and R11 IP21 236 Dimension drawings ...
Страница 237: ...Frames R10 and R11 B054 IP42 UL Type 1 Dimension drawings 237 ...
Страница 238: ...Frames R10 and R11 B055 IP54 UL Type 12 238 Dimension drawings ...
Страница 239: ...Frames R10 and R11 F289 T Dimension drawings 239 ...
Страница 240: ...Frames R10 and R11 H351 H353 240 Dimension drawings ...
Страница 241: ...Frames R10 and R11 B054 IP42 UL type 1 H351 H353 T Dimension drawings 241 ...
Страница 242: ...Frames R10 and R11 B055 IP54 UL type 12 H351 H353 T 242 Dimension drawings ...
Страница 257: ... Declaration of conformity The Safe torque off function 257 ...
Страница 269: ...Setting Parameter 1 s 15 09 RO4 OFF delay Optional I O extension modules 269 ...