Availability of du/dt filter and common mode filter by drive or inverter type
Availability of common mode filter
(CMF)
Availability of du/dt filter
Product type
+E208
+E205
ACS580-07
Additional requirements for explosion-safe (EX) motors
If you will use an explosion-safe (EX) motor, follow the rules in the requirements table above.
In addition, consult the motor manufacturer for any further requirements.
Additional requirements for ABB motors of types other than M2_, M3_, M4_, HX_ and
AM_
Use the selection criteria given for non-ABB motors.
Additional requirements for braking applications
When the motor brakes the machinery, the intermediate circuit DC voltage of the drive
increases, the effect being similar to increasing the motor supply voltage by up to 20 percent.
Consider this voltage increase when specifying the motor insulation requirements if the
motor will be braking a large part of its operation time.
Example: Motor insulation requirement for a 400 V AC line voltage application must be
selected as if the drive were supplied with 480 V.
Additional requirements for the regenerative and low harmonics drives
It is possible to increase the intermediate circuit DC voltage from the nominal (standard)
level with a parameter in the control program. If you choose to do this, select the motor
insulation system which withstands the increased DC voltage level.
Additional requirements for ABB high-output and IP23 motors
The rated output power of high output motors is higher than what is stated for the particular
frame size in EN 50347 (2001).
This table shows the requirements for protecting the motor insulation and bearings in drive
systems for ABB random-wound motor series (for example, M3AA, M3AP and M3BP).
Requirement for
Nominal AC supply
voltage
ABB du/dt and common mode filters, insulated N-end motor
bearings
Motor insulation
system
P
N
≥ 200 kW
100 kW ≤ P
N
<
200 kW
P
N
< 100 kW
P
N
≥ 268 hp
140 hp ≤ P
N
<
268 hp
P
N
< 140 hp
+ N + CMF
+ N
-
Standard
U
N
≤ 500 V
+ d
u
/d
t
+ N + CMF
+ d
u
/d
t
+ N
+ d
u
/d
t
Standard
500 V <
U
N
≤ 600 V
or
+ N + CMF
+ N
-
Reinforced
+ d
u
/d
t
+ N + CMF
+ d
u
/d
t
+ N
+ d
u
/d
t
Reinforced
600 V <
U
N
≤ 690 V
Additional requirements for non-ABB high-output and IP23 motors
The rated output power of high-output motors is higher than what is stated for the particular
frame size in EN 50347 (2001).
Guidelines for planning the electrical installation 67
11
Содержание ACS580-07
Страница 1: ... ABB GENERAL PURPOSE DRIVES ACS580 07 Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 14: ...14 ...
Страница 21: ...Measuring points of frames R6 to R9 are shown below PE L1 L2 L3 Safety instructions 21 ...
Страница 26: ...26 ...
Страница 30: ...30 ...
Страница 50: ...50 ...
Страница 62: ...62 ...
Страница 95: ...Electrical installation 95 11 ...
Страница 101: ...Electrical installation 101 11 ...
Страница 114: ...114 ...
Страница 124: ...Note Only 24 V DC can be used for STO Only PNP input configuration can be used 124 Control unit ...
Страница 128: ...128 ...
Страница 134: ...134 ...
Страница 142: ...142 Maintenance ...
Страница 155: ...3 4 5 Maintenance 155 ...
Страница 157: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 157 ...
Страница 161: ...4 5 3 Maintenance 161 ...
Страница 163: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 163 ...
Страница 169: ...1 2 3 5a 5b CR2032 Maintenance 169 ...
Страница 170: ...170 ...
Страница 185: ...Frame R6 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 185 ...
Страница 186: ...Frame R6 Input and motor cable terminal dimensions option F289 DET A 186 Technical data ...
Страница 190: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS250 DET A 190 Technical data ...
Страница 191: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 191 ...
Страница 192: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit option F289 192 Technical data ...
Страница 193: ...Frames R6 and R7 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 193 ...
Страница 196: ...Frame R8 Input and motor cable terminal dimensions bottom entry and exit option F289 196 Technical data ...
Страница 199: ...Frames R8 and R9 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 199 ...
Страница 201: ...Frame R9 Input and motor cable terminal dimensions option F289 Technical data 201 ...
Страница 202: ...Frame R10 Input and motor cable terminal dimensions bottom entry and exit 202 Technical data ...
Страница 203: ...Frame R10 Input and motor cable terminal dimensions bottom entry and exit option E205 Technical data 203 ...
Страница 204: ...Frame R10 Input and motor cable terminal dimensions top entry and exit 204 Technical data ...
Страница 205: ...Frame R10 Input and motor cable terminal dimensions top entry and exit option F289 Technical data 205 ...
Страница 206: ...Frame R11 Input and motor cable terminal dimensions bottom entry and exit 206 Technical data ...
Страница 207: ...Frame R11 Input and motor cable terminal dimensions bottom entry and exit option E205 Technical data 207 ...
Страница 208: ...Frame R11 Input and motor cable terminal dimensions top entry and exit 208 Technical data ...
Страница 209: ...Frame R11 Input and motor cable terminal dimensions top entry and exit option F289 Technical data 209 ...
Страница 217: ...Declaration of Conformity Technical data 217 ...
Страница 218: ...218 Technical data ...
Страница 223: ...Dimension drawings Example dimension drawings are shown below 13 Dimension drawings 223 ...
Страница 224: ...Frames R6 and R7 IP21 UL Type 1 224 Dimension drawings ...
Страница 225: ...Frames R6 and R7 B054 IP42 UL Type 1 Dimension drawings 225 ...
Страница 226: ...Frames R6 and R7 B055 IP54 UL Type 12 226 Dimension drawings ...
Страница 227: ...Frames R6 and R7 H351 and H353 top entry and exit Dimension drawings 227 ...
Страница 228: ...Frames R6 and R7 F289 228 Dimension drawings ...
Страница 229: ...Frames R6 and R7 F289 H351 H353 Dimension drawings 229 ...
Страница 230: ...Frames R8 and R9 IP21 230 Dimension drawings ...
Страница 231: ...Frames R8 and R9 B054 IP42 UL Type 1 Dimension drawings 231 ...
Страница 232: ...Frames R8 and R9 B055 IP54 UL Type 12 232 Dimension drawings ...
Страница 233: ...Frames R8 and R9 H351 and H353 top entry and exit Dimension drawings 233 ...
Страница 234: ...Frames R8 and R9 F289 234 Dimension drawings ...
Страница 235: ...Frames R8 and R9 F289 H351 H353 Dimension drawings 235 ...
Страница 236: ...Frames R10 and R11 IP21 236 Dimension drawings ...
Страница 237: ...Frames R10 and R11 B054 IP42 UL Type 1 Dimension drawings 237 ...
Страница 238: ...Frames R10 and R11 B055 IP54 UL Type 12 238 Dimension drawings ...
Страница 239: ...Frames R10 and R11 F289 T Dimension drawings 239 ...
Страница 240: ...Frames R10 and R11 H351 H353 240 Dimension drawings ...
Страница 241: ...Frames R10 and R11 B054 IP42 UL type 1 H351 H353 T Dimension drawings 241 ...
Страница 242: ...Frames R10 and R11 B055 IP54 UL type 12 H351 H353 T 242 Dimension drawings ...
Страница 257: ... Declaration of conformity The Safe torque off function 257 ...
Страница 269: ...Setting Parameter 1 s 15 09 RO4 OFF delay Optional I O extension modules 269 ...