Fault tracing   

17

5091

Safe torque off

Programmable fault: 

31.22

 

STO indication run/stop

Safe torque off function is 
active, ie. safety circuit 
signal(s) connected to 
connector STO is broken 
during start or run.

Check safety circuit connections. For 
more information, see chapter 

The Safe 

torque off function

 in the 

Hardware 

manual

 of the drive and description of 

parameter 

31.22

 

STO indication run/stop

 

(page 

244

).

Check the value of parameter 

95.04

 

Control board supply

.

5092

PU logic error

Power unit memory has 
cleared.

Contact your local ABB representative.

5093

Rating ID mismatch

The hardware of the drive does 
not match the information 
stored in the memory. This 
may occur e.g. after a firmware 
update.

Cycle the power to the drive. You may 
have to be repeat this. 

5094

Measurement circuit 
temperature

Problem with internal 
temperature measurement of 
the drive.

Contact your local ABB representative.

5089

SMT circuit 
malfunction

Safe motor temperature fault is 
generated and STO
event/fault/warning is not 
generated.

Note:

 If only one STO channel 

is opened, fault 

5090

 

STO 

hardware failure

 is generated.

Check connection between the relay 
output of the module and the STO 
terminal.

5098

I/O communication 
loss

Communication failure to 
standard I/O.

Try resetting the fault or cycle the power 
to the drive.

50A0

Fan

Cooling fan stuck or 
disconnected.

Check fan operation and connection.
Replace fan if faulty.

5682

Power unit lost

Connection between the drive 
control unit and the power unit 
is lost.

Check the connection between the 
control unit and the power unit.

5691

Measurement circuit 
ADC

Measurement circuit fault.

Contact your local ABB representative.

5692

PU board powerfail

Power unit power supply 
failure.

Contact your local ABB representative.

5693

Measurement circuit 
DFF

Measurement circuit fault.

Contact your local ABB representative.

5696

PU state feedback

State feedback from output 
phases does not match control 
signals.

Contact your local ABB representative.

5697

Charging feedback

Charging feedback signal 
missing.

Check the feedback signal coming from 
the charging system

5698

Unknown PU fault

The power unit logic has 
generated a fault which is not 
known by the software.

Check the logic and software 
compatibility.

6181

FPGA version 
incompatible

Firmware and FPGA versions 
are incompatible.

Reboot the control unit (using parameter 

96.08

 

Control board boot

) or by cycling 

power. If the problem persists, contact 
your local ABB representative

6306

FBA A mapping file

Fieldbus adapter A mapping 
file read error.

Contact your local ABB representative.

Code
(hex)

Fault / Aux. code

Cause

What to do

Содержание ACS480

Страница 1: ...ABB GENERAL PURPOSE DRIVES ACS480 Fault tracing Troubleshooting...

Страница 2: ...ables Each table is sorted by warning fault code Safety WARNING Only qualified electricians are allowed to service the drive Read the instructions in chapter Safety instructions at the beginning of th...

Страница 3: ...The codes of these events are included in the Warning messages table on page 388 Editable messages For external events the action fault or warning name and the message text can be edited To specify e...

Страница 4: ...4 Warnings and faults page 161 The event log can also be accessed and reset using the Drive composer PC tool See Drive composer PC tool user s manual 3AUA0000094606 English QR code generation for mobi...

Страница 5: ...d delta star connection Check for an earth fault in motor or motor cables by measuring the insulation resistances of motor and motor cable See chapter Electrical installation section Checking the insu...

Страница 6: ...ur local ABB representative A3A2 DC link undervoltage Intermediate circuit DC voltage too low when the drive is stopped A3AA DC not charged The voltage of the intermediate DC circuit has not yet risen...

Страница 7: ...temperature difference between the IGBTs of different phases Check the motor cabling Check cooling of drive module s A4F6 IGBT temperature Drive IGBT temperature is excessive Check ambient conditions...

Страница 8: ...sion ZZZ specifies the flash subsector number that generated the warning A6A4 Motor nominal value The motor parameters are set incorrectly Check the auxiliary code See actions for each code below The...

Страница 9: ...control unit or parameter 12 15 12 25 Note Control unit reboot either by cycling the power or through parameter 96 08 Control board boot is required to validate any changes in the hardware settings A6...

Страница 10: ...perature has exceeded internal warning limit Let chopper cool down Check for excessive ambient temperature Check for cooling fan failure Check for obstructions in the air flow Check the dimensioning a...

Страница 11: ...nsider changing the cooling fan Parameter 05 04 Fan on time counter shows the running time of the cooling fan A8A0 AI supervision Programmable warning 12 03 AI supervision function An analog signal is...

Страница 12: ...ge text Programmable warning 32 56 Supervision 6 action Warning generated by the signal supervision function 6 Check the source of the warning parameter 32 57 Supervision 6 signal A8BE ULC overload wa...

Страница 13: ...l page 114 and parameters 40 43 40 48 AFAA Autoreset A fault is about to be autoreset Informative warning See the settings in parameter group 31 Fault functions AFE1 Emergency stop off2 Drive has rece...

Страница 14: ...n run stop page 244 D501 No more available PFC motors No more PFC motors can be started because they can be interlocked or in the Hand mode Check that there are no interlocked PFC motors see parameter...

Страница 15: ...Check there are no contactors opening and closing in motor cable Check that the start up data in parameter group 99 corresponds to the motor rating plate Check that there are no power factor correctio...

Страница 16: ...ly voltage matches the nominal input voltage of the drive Check the supply line for static or transient overvoltage Check brake chopper and resistor if present Check deceleration time Use coast to sto...

Страница 17: ...age text Measured temperature 1 has exceeded fault limit Check the value of parameter 35 02 Measured temperature 1 Check the cooling of the motor or other equipment whose temperature is being measured...

Страница 18: ...n loss Communication failure to standard I O Try resetting the fault or cycle the power to the drive 50A0 Fan Cooling fan stuck or disconnected Check fan operation and connection Replace fan if faulty...

Страница 19: ...ause parameter default value that cannot be changed has been attempted to write 64E1 Kernel overload Operating system error Reboot the control unit using parameter 96 08 Control board boot or by cycli...

Страница 20: ...drive has ceased communicating Check PC tool or control panel connection Check control panel connector Disconnect and reconnect the control panel 7085 Incompatible option module Fieldbus option modul...

Страница 21: ...le fault 50 02 FBA A comm loss func Cyclical communication between drive and fieldbus adapter module A or between PLC and fieldbus adapter module A is lost Check status of fieldbus communication See u...

Страница 22: ...device Check setting of parameter 31 01 External event 1 source 9082 External fault 2 Editable message text Programmable fault 31 03 External event 2 source 31 04 External event 2 type Fault in extern...

Страница 23: ...2 Maximum speed 99 07 Motor nominal voltage 99 08 Motor nominal frequency 99 09 Motor nominal speed Make sure that 30 12 0 55 99 09 0 50 synchronous speed 30 11 0 and supply voltage 0 66 99 07 0003 Ma...

Страница 24: ...ve 0013 Asynchronous motors only Motor data error Check that the motor nominal value settings in the drive are the same as in the motor nameplate Contact your local ABB representative FF63 STO diagnos...

Отзывы: