DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
1602 PARAMETER
LOCK
Selects the state of the parameter lock. The lock prevents
parameter changing from the control panel.
LOCKED
Parameter values cannot be changed from the control
panel. The lock can be opened by entering the valid code to
parameter
The lock does not prevent parameter changes made by
macros or fieldbus.
0
OPEN
The lock is open. Parameter values can be changed.
1
NOT SAVED
Parameter changes from the control panel are not stored
into the permanent memory. To store changed parameter
values, set parameter
value to
2
1603 PASS CODE
Selects the pass code for the parameter lock (see
parameter
).
0
0…65535
Pass code. Setting 358 opens the lock. The value reverts
back to 0 automatically.
1 = 1
1604 FAULT RESET
SEL
Selects the source for the fault reset signal. The signal
resets the drive after a fault trip if the cause of the fault no
longer exists.
KEYPAD
Fault reset only from the control panel
0
DI1
Reset through digital input DI1 (reset on the rising edge of
DI1) or from the control panel
1
DI2
See selection
2
DI3
See selection
3
DI4
See selection
4
DI5
See selection
5
START/STOP
Reset along with the stop signal received through a digital
input, or from the control panel.
Note:
Do not use this option when start, stop and direction
commands are received through fieldbus communication.
7
COMM
Fieldbus interface as the source for the fault reset signal, ie,
Control word
profile
bit 7). The Control word is sent by
the fieldbus controller through the fieldbus adapter or
embedded fieldbus (Modbus) to the drive. For the Control
word bits, see sections
on page
ABB drives communication profile
on page
.
8
DI1(INV)
Reset through inverted digital input DI1 (reset on the falling
edge of DI1) or from the control panel
-1
DI2(INV)
See selection
-2
All parameters
No.
Name/Value
Description
Def/FbEq
Содержание ACS355 series
Страница 1: ...ABB machinery drives User s manual ACS355 drives ...
Страница 4: ......
Страница 16: ...16 ...
Страница 32: ...32 Operation principle and hardware description ...
Страница 58: ...58 Electrical installation ...
Страница 74: ...74 Start up control with I O and ID run ...
Страница 106: ...106 Control panels ...
Страница 120: ...120 Application macros ...
Страница 178: ...178 Program features ...
Страница 338: ...338 Fieldbus control with embedded fieldbus ...
Страница 368: ...368 Fault tracing ...
Страница 404: ...404 Dimension drawings ...
Страница 410: ...410 Appendix Resistor braking ...
Страница 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...
Страница 436: ...3AUA0000066143 Rev D EN EFFECTIVE 2018 01 01 Contact us www abb com drives www abb com drivespartners ...