Actual signals and parameters 205
14 RELAY OUTPUTS
Status information indicated through relay output, and relay
operating delays.
Note:
Relay outputs 2…4 are available only if the MREL-01
output relay module is connected to the drive. See
MREL-
01 output relay module user's manual
(3AUA0000035974
[English]).
1401 RELAY
OUTPUT 1
Selects a drive status indicated through relay output RO 1.
The relay energizes when the status meets the setting.
NOT SEL
Not used
0
READY
Ready to function: Run enable signal on, no fault, supply
voltage within acceptable range and emergency stop signal
off.
1
RUN
Running: Start signal on, Run enable signal on, no active
fault.
2
FAULT(-1)
Inverted fault. Relay is de-energized on a fault trip.
3
FAULT
Fault
4
ALARM
Alarm
5
REVERSED
Motor rotates in reverse direction.
6
STARTED
The drive has received start command. Relay is energized
even if Run enable signal is off. Relay is de-energized when
drive receives a stop command or a fault occurs.
7
SUPRV1
OVER
Status according to supervision parameters
…
See parameter group
.
8
SUPRV1
UNDER
See selection
9
SUPRV2
OVER
Status according to supervision parameters
…
See parameter group
.
10
SUPRV2
UNDER
See selection
11
SUPRV3
OVER
Status according to supervision parameters
…
See parameter group
.
12
SUPRV3
UNDER
See selection
13
AT SET POINT Output frequency is equal to the reference frequency.
14
FAULT(RST)
Fault. Automatic reset after the autoreset delay. See
parameter group
.
15
FLT/ALARM
Fault or alarm
16
EXT CTRL
Drive is under external control.
17
REF 2 SEL
External reference REF 2 is in use.
18
CONST FREQ A constant speed is in use. See parameter group
.
19
All parameters
No.
Name/Value
Description
Def/FbEq
Содержание ACS355 series
Страница 1: ...ABB machinery drives User s manual ACS355 drives ...
Страница 4: ......
Страница 16: ...16 ...
Страница 32: ...32 Operation principle and hardware description ...
Страница 58: ...58 Electrical installation ...
Страница 74: ...74 Start up control with I O and ID run ...
Страница 106: ...106 Control panels ...
Страница 120: ...120 Application macros ...
Страница 178: ...178 Program features ...
Страница 338: ...338 Fieldbus control with embedded fieldbus ...
Страница 368: ...368 Fault tracing ...
Страница 404: ...404 Dimension drawings ...
Страница 410: ...410 Appendix Resistor braking ...
Страница 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...
Страница 436: ...3AUA0000066143 Rev D EN EFFECTIVE 2018 01 01 Contact us www abb com drives www abb com drivespartners ...