Electrical installation 53
Default I/O connection diagram
The default connection of the control signals depends on the application macro in
use, which is selected with parameter
.
The default macro is the HVAC Default. It provides a general purpose I/O
configuration with three constant speeds. Parameter values are the default values
given in section
Parameters in the short parameter view
on page
. For information
on other macros, see section
on page
The default I/O connections for the ABB standard macro are given in the figure below.
X1A
1
SCR
Signal cable shield (screen)
2
AI1
External reference
: 0…10 V or 0...20 mA
3
GND
Analog input circuit common
4
+10V
Reference voltage: +10 V DC, max. 10 mA
5
AI2
PID feedback 0…10 V or 0...20 mA
6
GND
Analog input circuit common
7
AO
Output frequency value
: 0…20 mA
8
GND
Analog output circuit common
9
+24V
Auxiliary voltage output: +24 V DC, max. 200 mA
10 GND
Auxiliary voltage output common
11 DCOM
Digital input common
12 DI1
Stop (0) / Start (1)
13 DI2
Not Configured
14 DI3
Constant speed selection
1)
15 DI4
Safety Interlock
16 DI5
Not Configured
X1B
17 ROCOM
Relay output 1
Default operation: Ready
18 RONC
19 RONO
20 DOSRC
Digital output, max. 100 mA
No fault [Fault (-1)]
21 DOOUT
22 DOGND
max. 500 ohm
1…10 kohm
: 2) 360 degree grounding under a clamp.
Tightening torque: 0.4 N·m (3.5 lbf·in).
DI3 Operation (parameter)
0
Set speed through AI1
1
Speed 1 (
0
Speed 2 (
1
Speed 3 (
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...