264 Actual signals and parameters
8111
START FREQ 3
0.0 … 500.0 Hz
0.1 Hz
60.0
Sets the frequency limit used to start the third auxiliary motor.
• See parameter
1for a complete description of the operation.
The third auxiliary motor starts if:
• Two auxiliary motors are running.
• ACS320 output frequency exceeds the limit: 8111 START FREQ 3 + 1 Hz.
• Output frequency stays above the relaxed limit (8111 START FREQ 3 - 1 Hz) for at
least the time:
8112
LOW FREQ 1
0.0 … 500.0 Hz
0.1 Hz
25.0
Sets the frequency limit used to stop the first auxiliary motor. The first auxiliary motor
stops if:
• First auxiliary motor is running
alone.
• ACS320 output frequency
drops below the limit:
8112 LOW FREQ 1 - 1.
• Output frequency stays below
the relaxed limit
(8112 LOW FREQ 1 + 1 Hz)
for at least the time:
After the first auxiliary motor
stops:
• Output frequency increases
by the value =
(
) -
(8112 LOW FREQ 1).
• In effect, the output of the speed regulated motor increases to compensate for the
loss of the auxiliary motor.
See the figure, where:
• A = (
) - (8112 LOW FREQ 1)
• B = Output frequency decrease during the stop delay.
• C = Diagram showing auxiliary motor’s run status as frequency decreases (1 = On).
• Grey path = Shows hysteresis – if time is reversed, the path backwards is not the
same. For details on the path for starting, see the diagram at
.
Note:
Low Frequency 1 value must be between:
• (
).
•
Group 81: PFA control
Code
Description
Range
Resolution
Default
S
t
B
f (Hz)
f
MAX
f
MIN
t
1
0
C
A
A
8112
(
)- 1
Содержание ACS320 series
Страница 1: ...ABB drives User s manual ACS320 drives 0 5 to 30 hp ...
Страница 4: ......
Страница 18: ...18 Safety ...
Страница 28: ...28 Operation principle and hardware description ...
Страница 56: ...56 Electrical installation ...
Страница 142: ...142 Program features Connection diagram example ACS320 xx xxxx x ...
Страница 282: ...282 Actual signals and parameters ...
Страница 358: ...358 Fieldbus control ...
Страница 376: ...376 Fault tracing ...
Страница 382: ...382 Maintenance and hardware diagnostics ...
Страница 407: ...Dimension drawings 407 Frame size R2 NEMA 1 Frame size R2 IP20 NEMA 1 3AUA0000051097 A ...
Страница 409: ...Dimension drawings 409 Frame size R3 NEMA 1 Frame size R3 IP20 NEMA 1 3AUA0000051118 A ...
Страница 411: ...Dimension drawings 411 Frame size R4 NEMA 1 Frame size R4 IP20 NEMA 1 3AUA0000051133 A ...
Страница 412: ...412 Dimension drawings ...
Страница 413: ...Index Numerics A B C D E F G H I K L M N O P R S T ...
Страница 442: ...www abb com drives www abb com drivespartners 3AUA0000062599 Rev E EN EFFECTIVE 2016 07 05 Contact us 3AUA0000062599E ...