5-8 (14)
2UEA001270 Rev. F
ACS2000 User manual
Chapter 5 - Mechanical installation
.
Figure 5-6 - Frame 1 Redundant fan box
2
Remove the fan hole cover plate or the fan outlet box (if installed)
from the top of the drive.
3
Lift and properly orientate the empty redundant fan box on top of the
drive, being careful not to damage the sealing gasket.
.
Figure 5-7 - Frame 1 Redundant fan installation
4
Fasten the fan unit using the supplied screws. The predrilled holes
(see Figure 5-7 - Frame 1) are fitted with press nuts on the underside.
5
Make the terminal block to drive wiring connections.
The front wall of the fan box may be removed for easier access to the
wiring.
A
Remove the upper IFU (Input Filter Unit) panel to access the
drive wiring for the redundant fan.
B
Carefully feed the wires from the drive up into the fan unit
housing and route to the terminal block.
C
Make the wiring connections.
Legend
1
Redundant fan
housing
2
Sealing gasket
3
Predrilled holes
4
Drive’s redundant
fan wiring
5
Terminal block
Содержание ACS2000 DFE
Страница 1: ...Medium Voltage Drives User Manual ACS2000 4 kV ...
Страница 2: ......
Страница 12: ...LOF 4 4 2UEA001270 Rev F ACS2000 User manual ...
Страница 14: ...LOT 2 2 2UEA001270 Rev F ACS2000 User manual ...
Страница 40: ...1 12 12 2UEA001270 Rev F ACS2000 User manual Chapter 1 Safety ...
Страница 68: ...2 28 28 2UEA001270 Rev F ACS2000 User manual Chapter 2 Power electronics and cabinet features ...
Страница 94: ...3 26 26 2UEA001270 Rev F ACS2000 User manual Chapter 3 Control system ...
Страница 116: ...5 14 14 2UEA001270 Rev F ACS2000 User manual Chapter 5 Mechanical installation ...
Страница 134: ...7 2 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Страница 138: ...7 6 6 2UEA001270 Rev F ACS2000 User manual Chapter 7 Commissioning ...
Страница 156: ...8 18 18 2UEA001270 Rev F ACS2000 User manual Chapter 8 Local operation ...
Страница 213: ......