128 Parameters
Selects the digit outputs that will be controlled by
parameter
. The signals connected to the digit
outputs can be overridden for eg. testing purposes. A bit
in parameter
is provided for each
digit output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
and
).
0000h
0000h...FFFFh
Forced selections of digital inputs/outputs.
1=1
Contains the values of digit outputs that are used instead
of the connected signals if selected in parameter
. Bit 0 is the forced value for DO1.
This provides the possibility to test the drive functionality
without the plant wiring. T
on
and T
off
delays are passed.
0000h
0000h...FFFFh
Forced values of digital outputs.
1=1
Selects a drive signal to be connected to digital output
DO1.
Not energized
Output is not energized.
0
Energized
Output is energized.
1
Ready run
Bit 1 of
Enabled
Bit 0 of
4
Started
Bit 5 of
5
Magnetized
6
Running
Bit 6 of
7
Ready ref
Bit 2 of
8
At setpoint
9
Reverse
Bit 2 of
.
10
Zero speed
Bit 0 of
.
11
Above limit
Bit 10 of
12
Warning
Bit 7 of
13
Fault
14
Fault (-1)
Inverted bit 3 of
.
15
Fault/Warning
A warning or fault is active.
16
Overcurrent
A drive is tripped to overcurrent fault.
17
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1 = Force DO1 to value of bit 0 of parameter
.
1...15
Reserved
Bit
Value
0
1 = Force the value of this bit to DO1, if so defined in parameter 11.03 DO force
selection.
1...15
Reserved