Parameters 125
Defines the deactivation delay for digital output DI4. See
parameter
0.0 -
0.0 … 3000.0 s
Deactivation delay for DI4.
10 = 1 -
Defines the activation delay for digital output DI5. See
parameter
0.0 -
0.0 … 3000.0 s
Activation delay for DI5.
10 = 1 -
Defines the deactivation delay for digital output DI5. See
parameter
0.0 -
0.0 … 3000.0 s
Deactivation delay for DI5.
10 = 1 -
Status of relay outputs RO1.
-
0000h…FFFFh
Status of relay outputs.
1 = 1
Selects the relay outputs that will be controlled by
parameter
. The signals connected to the relay
outputs can be overridden for eg. testing purposes. A bit in
parameter
is provided for each relay
output, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
).
0000h
0000h…FFFFh
Override selection for relay outputs.
1 = 1
Contains the values of relay outputs that are used instead
of the connected signals if selected in parameter
. Bit 0 is the forced value for RO1.
This provides the possibility to test the drive functionality
without the plant wiring. Ton and Toff delays are passed.
0000h…FFFFh
Forced RO values.
1 = 1
Selects a drive signal to be connected to relay output
RO1.
Not energized
Output is not energized.
0
Energized
Output is energized.
1
Ready run
Bit 1 of
. 2
Enabled
Bit 0 of
4
No.
Name/Value
Description
Default
FbEq 16
Bit
Value
0
1 = RO1 is energized.
1...15 Reserved.
Bit
Value
0
1 = Force RO1 to value of bit 0 of parameter
(0 = Normal mode).
1…15
Reserved
Bit
Value
0
Forced value (0 or 1) for parameter
.
1…15
Reserved
ACS180 FW.book Page 125 Tuesday, March 9, 2021 2:25 PM