Actual signals and parameters
211
EDIT
Stop to edit mode. Program can be edited.
3
83.02
EDIT COMMAND
Selects the command for the block placed in the location defined with
parameter
. The program must be in the editing mode (see parameter
NO
Home value. The value automatically restores to NO after an editing command
has been executed.
1
PUSH
Shifts the block in location defined with parameter
and the following
blocks one location up. A new block can be placed in the emptied location by
programming the Block Parameter Set as usual.
Example:
A new block needs to be placed in between the current block
number four (parameters 84.20 … 84.25) and five (parameters 84.25 …
84.29).
In order to do this:
- Shift the program to the editing mode with parameter
.
- Select location number five as the desired location for the new block with
parameter
- Shift the block in location number 5 and the following blocks one location
forward with parameter
. (selection PUSH)
- Program the emptied location number 5 with parameters 84.25 to 84.29 as
usual.
2
DELETE
Deletes the block in location defined with parameter
and shifts the
following blocks one step down.
3
PROTECT
Activation of the Adaptive Program protection. Activate as follows:
- Ensure the Adaptive Program operation mode is START or STOP (parameter
).
- Change parameter
to PROTECT.
When activated:
- All parameters in group 84 excluding the block output parameters are hidden
(read protected).
- It is not possible to switch the program to the editing mode (parameter
).
is set to 0.
4
UNPROTECT
Inactivation of the Adaptive Program protection. Inactivate as follows:
- Ensure the Adaptive Program operation mode is START or STOP (parameter
).
- Change parameter
to UNPROTECT.
Note:
If the passcode is lost, it is possible to reset the protection also by
changing the application macro setting (parameter
APPLICATION
MACRO).
5
83.03
EDIT BLOCK
Defines the block location number for the command selected with parameter
1 … 15
Block location number
1 = 1
83.04
TIMELEVEL SEL
Selects the execution cycle time for the Adaptive Program. The setting is valid
for all blocks.
12 ms
12 milliseconds
1
100 ms
100 milliseconds
2
1000 ms
1000 milliseconds
3
Index
Name/Selection
Description
FbEq
Содержание ACS 800 Series
Страница 1: ...ACS800 Firmware Manual Crane Control Program N697 ...
Страница 4: ......
Страница 26: ...Start up and control through the I O interface 26 ...
Страница 36: ...Quick start up guide 36 ...
Страница 52: ...Control panel 52 ...
Страница 105: ...Program features 105 Figure Control diagram for Shaft synchronisation executed in 20 ms ...
Страница 126: ...Program features 126 The figures below show speed limits according to different load conditions ...
Страница 128: ...Program features 128 ...
Страница 150: ...Application macros control location EXT1 EXT2 150 ...
Страница 228: ...Actual signals and parameters 228 ...
Страница 299: ...Adaptive Programming examples for crane control 299 ...
Страница 305: ...Adaptive Programming examples for crane control 305 ...
Страница 312: ...Adaptive Programming examples for crane control 312 The following figures show the previous example enlarged ...
Страница 314: ...Adaptive Programming examples for crane control 314 The following figures show the previous example enlarged ...
Страница 318: ...Analogue Extension Module 318 ...
Страница 332: ...Additional data actual signals and parameters 332 ...
Страница 333: ...DriveWindow 333 DriveWindow DriveWindow connected to the ACS800 RMIO RDCO board and channel CH3 ...
Страница 334: ...DriveWindow 334 ...
Страница 335: ...Control block diagrams 335 Control block diagrams ...
Страница 336: ...Control block diagrams 336 ...
Страница 337: ...Control block diagrams 337 ...
Страница 338: ...Control block diagrams 338 ...
Страница 340: ...www abb com drives www abb com drivespartners Contact us 3AFE68775230 Rev E EN 2012 09 25 ...