89
Technical Data
Cooling
Method
Internal fan, flow direction from front to top
Filter material
Inlet (door)
Outlet (roof)
UL Type 12
3AUA0000006723 (qty 1)
3AUA0000006722 (qty 2)
Note:
When installing the filter media, the white side must face the outside of the cabinet
and the colored side must face the inside of the cabinet
Free space around the unit
See
"Free Space Around the Unit"
.
Cooling air flow
See
"NEMA Ratings"
.
Degrees of Protection
UL type 1, UL type 1 Filtered, UL type 12
Ambient Conditions
Environmental limits for the drive are given below. The drive is to be used in a heated,
indoor, controlled environment.
Operation
installed for stationary use
Storage
in the protective package
Transportation
in the protective package
Installation site altitude
0 to 4000 m (13123 ft)
above sea level [above
1000 m (3281 ft), see
section
"Derating"
]
-
-
Air temperature
-15 to +50 °C (5 to 122 °F).
See section
"Derating".
-40 to +70 °C (-40 to
+158 °F)
-40 to +70 °C (-40 to
+158 °F)
Relative humidity
5 to 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
Contamination levels
(IEC 60721-3-3, IEC 60721-
3-2, IEC 60721-3-1)
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C1
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Atmospheric pressure
70 to 106 kPa
0.7 to 1.05 atmospheres
70 to 106 kPa
0.7 to 1.05 atmospheres
60 to 106 kPa
0.6 to 1.05 atmospheres
Vibration
(IEC 60068-2)
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz) sinusoidal
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
max. 7 m/s
2
(23 ft/s
2
)
(13.2 to 100 Hz) sinusoidal
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
max. 15 m/s
2
(49 ft/s
2
)
(9 to 200 Hz) sinusoidal
Shock
(IEC 60068-2-29)
Not allowed
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Max. 100 m/s
2
(330 ft./s
2
),
11 ms
Free fall
Not allowed
100 mm (4 in.) for weight
over 100 kg (220 lb)
100 mm (4 in.) for weight
over 100 kg (220 lb)