61
Installation Checklist and Start-Up
Start-Up Procedure
Action
Additional information
Safety
Only qualified electricians are allowed to start-up the drive. The safety
instructions must be followed during the start-up procedure.
See chapter
"Safety Instructions"
.
Checks with no voltage connected
Check the tuning of the insulation monitoring device.
Optional device. See delivery
specific circuit diagrams and
IRDH265 Operating Manual
by
Bender (code: TGH1249).
Pt 100 settings (if present)
Starting the drive
Close the switch fuse (main disconnector).
Units with line contactor: Close the contactor by turning the start switch
on the cabinet door from OFF into START position for 2 seconds. Leave
the switch to ON position.
Application program set-up
Follow the instructions in the
Firmware Manual
to start up the drive and
to set the drive parameters.
On-load checks
Check that the Prevention of Unexpected Start function (if installed)
works:
• Start and Stop the drive and wait until the motor has stopped.
• Open the Prevention of Unexpected Start switch (mounted on a control
desk). The indicating lamp should lit.
• Give a Start command. The drive should not start.
• Reset the drive from the control panel.
Optional function. See delivery
specific circuit diagrams.
Check that the cooling fans rotate freely in the right direction, and the air
flows upwards.
A paper sheet set on the intake
(door) gratings stays. The fans run
noiselessly.
Check the direction of rotation of the motor.
Check the correct operation of the emergency-stop circuits from each
operating location.