Start-up Guide
2
Standard Application Program
3 – START-UP DATA ENTERING (Parameter Group 99)
Select the language. The general parameter setting
procedure is given below.
The general parameter setting procedure:
• Press
PAR to select parameter mode.
• Press
or
to scroll Parameter Groups (10 to 99).
• Press
or
to scroll parameters within the
Parameter Group.
• Select a new value by
ENTER (brackets appear around
the parameter value) and
or
. (Fast change by
or .)
• Press
ENTER
to accept the new value (brackets
disappear).
Select the Application Macro. The general parameter
setting procedure is given above.
The default value FACTORY is suitable in most cases. A detailed
description of the Application Macros is included in
Firmware Manual.
Select the motor control mode. The general parameter
setting procedure is given above.
DTC is suitable in most cases. The SCALAR control mode is
recommended
• for multimotor drives when the number of motors connected to the
ACS 600 is variable.
• when the nominal current of the motor is less than 1/6 of the nominal
current of the inverter.
• when the inverter is used for test purposes with no motor connected.
START-UP PROCEDURE
1 -> 0.0 rpm O
99 START-UP DATA
01 LANGUAGE
ENGLISH
1 -> 0.0 rpm O
99 START-UP DATA
01 LANGUAGE
[ENGLISH]
1 -> 0.0 rpm O
99 START-UP DATA
02 APPLICATION MACRO
[ ]
1 -> 0.0 rpm O
99 START-UP DATA
04 MOTOR CTRL MODE
[DTC]