background image

 

Start-up Guide

Standard Application Program

1

START-UP PROCEDURE

1 – SAFETY

The start-up procedure must only be carried out by a qualified electrician.

The safety instructions must be followed during the start-up procedure. See the 
appropriate hardware manual for the safety instructions.

The ACx 600 must not be powered up more than five times in ten minutes to avoid 
charging resistor overheating (no limitation for ACS 600 MultiDrive and ACx 607 
units -0760-3, -0930-5, -0900-6 or above).

Check the installation before the start-up procedure. See the installation checklist from the 
appropriate hardware/installation manual.

Check that starting the motor does not cause any danger.

It is recommended having the driven equipment disengaged when first start is performed if 
there is the risk of damage to the driven equipment in case of incorrect rotation direction of 
the motor.

2 – POWER-UP

Apply mains power. The Control Panel first enters the 
panel identification data ...

...  then the Identification Display of the drive ...

...and after a few seconds the Control Panel automatically 
enters the Actual Signal Display.

Drive set-up can be started.

CDP312 PANEL   Vx.xx

   

.......

ACS 600       xx kW 

   

ID NUMBER 1

 1   ->   0.0 rpm  O

FREQ       0.00 Hz

CURRENT    0.00 A

POWER      0.00 %

Содержание ACS 600

Страница 1: ...Application Program 5 x ACS 600 Start up Guide This manual includes ACS 600 initialisation using the Control Panel First start Rotation direction check Start through a digital input Speed control usi...

Страница 2: ...his Guide describes the basic start up procedure of the ACS 600 frequency converter equipped with the Standard Application Program 5 x See the LUPZDUH 0DQXDO IRU 6 6WDQGDUG SSOLFDWLRQ 3URJUDP for more...

Страница 3: ...re the start up procedure See the installation checklist from the appropriate hardware installation manual Check that starting the motor does not cause any danger It is recommended having the driven e...

Страница 4: ...given above The default value FACTORY is suitable in most cases A detailed description of the Application Macros is included in Firmware Manual Select the motor control mode The general parameter set...

Страница 5: ...general parameter setting procedure is given on Page 2 Allowed range 1 6 I2hd 2 I2hd of ACS 600 Nominal frequency The general parameter setting procedure is given on Page 2 Range 8 300 Hz Nominal spee...

Страница 6: ...ro speed Operation at torque range above the motor nominal torque within wide speed range and without any pulse encoder i e without any measured speed feedback is required See the Firmware Manual for...

Страница 7: ...otor connection box Verify your work by applying mains power and repeating the check as described above 6 SPEED LIMITS AND ACCELERATION DECELERATION TIMES Set the minimum speed The general parameter s...

Страница 8: ...on the first row of the panel display Switch on digital input DI1 Drive starts The motor is accelerated to a speed determined by the voltage level of analogue input AI1 Valid if the factory macro is s...

Страница 9: ......

Страница 10: ...ABB Industry Oy Drives P O Box 184 FIN 00381 HELSINKI FINLAND Telephone 358 10 22 2000 Telefax 358 10 22 22681 3BFE 64049224 R0125 EFFECTIVE 26 08 1998 EN...

Отзывы: