Safety Instructions
14
ACS 600 MultiDrive
Fibre Optic Cables
WARNING!
Handle the fibre optic cables with care (especially when
joining the shipping splits). When unplugging optic cables, always grab
the connector, not the cable itself. Do not touch the ends of the fibres
with bare hands as the fibre is extremely sensitive to dirt.
Cooling
WARNING!
The cooling air flow and space requirements must be
fulfilled. Air flow from below (from a cable conduit) to the cabinet must
be prevented to ensure the degree of protection and fire protection.
Cable Type
Parameter
Minimum
Maximum
Unit
Plastic Optical Cable (POF, fibre core
diameter 1 mm):
Storage and Operating
Temperature
-55
+85
°C
Simplex
Recommended Operating
Temperature
-40
+85
°C
Installation Temperature
-20
+70
°C
Short Term Tensile Force
Simplex: 50
Duplex: 100
N
Duplex (zipcord)
Short Term Bend Radius
25
mm
Long Term Bend Radius
35
mm
Long Term Tensile Load
1
N
Flexing
1000
cycles
Hard Clad Silica Oval Shape Duplex Cable
(HCS
â
, SpecTran, fibre core diameter
200
m
m, outer dimensions 3.2 x 5.4 mm)
Storage Temperature
-40
+80
°C
Operating Temperature
-20
+80
°C
Short Term Tensile Force
46/205
lbs./N
Long Term Tensile Force
10/44
lbs./N
Bend Radius
25
mm
Hard Clad Silica 2-channel (Duplex) Cable
(HCS
â
, SpecTran, fibre core diameter
200
m
m, outer diameter 7.5 mm):
Storage and Operating
Temperature
-40
+85
°C
Short Term Tensile Force
46/205
lbs./N
Long Term Tensile Force
10/44
lbs./N
Bend Radius
75
mm
Optical fibre