248 Parameters
Enables the use of the motor disconnect switch.
When enabled, the drive does not trip to a fault
when it detects the disconnection but remains
operational and returns to normal operation
after a reconnection.
When this parameter is enabled, the drive will go
through the following sequence:
1. Motor is disconnected: Drive detects the
disconnection and indicates it with warning
. The drive remains in operation and waits
for motor reconnection.
2. Motor is reconnected: Drive detects the
reconnection, removes the warning and returns
to normal operation. The last active reference
before the disconnection is in use.
Note:
This feature is only available in scalar
mode. This parameter does not affect vector
mode behavior.
Disable
Motor disconnect switch disabled.
0
Enable
Motor disconnect switch enabled.
1
Selects the fan control type. The fan control
functionality enables heat dissipation from the
drive and avoids dust accumulation in the drive.
Auto
Controls the fan automatically according to the
temperature changes of the drive.
0
Always on
Fan runs continuously with the maximum speed
(50Hz).
1
96
Language selection; access levels; macro
selection; parameter save and restore; control
unit reboot; user parameter sets; unit selection.
Selects the language of the parameter interface
and other displayed information when viewed on
the control panel.
Notes
:
• Not all languages listed below are necessarily
supported.
• This parameter does not affect the languages
visible in the Drive composer PC tool. (Those
are specified under
View
–
Settings
–
Drive
default language
.)
Not
selected
Not selected
None.
0
English
English.
1033
Italiano
Italian.
1040
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...