240 Parameters
Warning/Fault
Outlet minimum pressure protection function
first generates a warning when the pressure is
below the level defined with parameter
Outlet minimum pressure warning level
for a time
set in parameter
.
If the pressure continues to fall below the level
defined with parameter
, outlet minimum pressure fault
is generated.
3
Outlet minimum
pressure warning
level
Defines the level at which drive should generate
the outlet minimum pressure warning.
0.00 bar
0.00...
32767.00 bar
Outlet minimum pressure warning level.
1 = 1 bar
Outlet minimum
pressure fault
level
Defines the level at which drive should generate
the outlet minimum pressure fault.
0.00 bar
0.00...
32767.00 bar
Outlet minimum pressure fault level.
1 = 1 bar
Outlet maximum
pressure
protection
Enables outlet maximum pressure protection
function.
Disabled
Outlet maximum pressure protection is disabled. 0
Warning
Outlet maximum pressure protection function
generates warning
when the pressure is above the level defined with
parameter
Outlet maximum pressure warning
for a time set in parameter
1
Fault
Outlet maximum pressure protection function
generates fault
when the pressure is above the level defined with
parameter
for a time set in parameter
2
Warning/Fault
Outlet maximum pressure protection function
first generates a warning when the pressure is
above the level defined with parameter
Outlet maximum pressure warning level
for a time
set in parameter
.
If the pressure raises above the level defined with
parameter
, outlet maximum pressure fault is
generated.
3
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...