146 Parameters
Selects which indications are given when one or
both Safe torque off (STO) signals are switched
off or lost. The indications also depend on
whether the drive is running or stopped when
this occurs.
The tables at each selection below show the
indications generated with that particular
setting.
Notes
:
• This parameter does not affect the operation
of the STO function itself. The STO function
will operate regardless of the setting of this
parameter: a running drive will stop upon
removal of one or both STO signals, and will
not start until both STO signals are restored
and all faults reset.
• The loss of only one STO signal always
generates a fault as it is interpreted as a
malfunction.
For more information on the STO, see chapter
The Safe torque off function
in the
Hardware
manual
of the drive.
Fault/Fault
0
No.
Name/Value
Description
Def/
FbEq16
Inputs
Indication (running or stopped)
IN1 IN2
0
0
Fault
0
1
Faults
1
0
Faults
1
1
(Normal operation)
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...