Parameters 139
Shows torque controller limitation status word.
This parameter is read-only.
0b0000
0b0000…
0b1111
Torque limitation status word.
1 = 1
Defines the drive current limit monitor time after
which action is taken as specified in the
parameter
10.00
0.00...120.00s
Current limit monitor time.
100=1
Selects how the drive reacts when the drive
reaches the current limit (
and exceeds the monitor time set by parameter
No action
None (current limit action disabled).
0
Warning
. 1
Fault
.
2
No.
Name/Value
Description
Def/
FbEq16
Bit
Name
Description
0
Undervoltage *1 = Intermediate DC circuit undervoltage
1
Overvoltage
*1 = Intermediate DC circuit overvoltage
2
Minimum
torque
*1 = Torque is being limited by
3
Maximum
torque
*1 = Torque is being limited by
4
Internal
current
1 = An inverter current limit (identified by bits 8…11) is
active
5
Load angle
(With permanent magnet motors and reluctance motors
only)
1 = Load angle limit is active, ie. the motor cannot
produce any more torque
6
Motor pullout (With asynchronous motors only)
Motor pull-out limit is active, ie. the motor cannot
produce any more torque
7
Reserved
8
Thermal
1 = Input current is being limited by the main circuit
thermal limit
9
Max current
*1 = Maximum output current (
I
MAX
) is being limited
10
User current
*1 = Output current is being limited by
11
Thermal IGBT *1 = Output current is being limited by a calculated
thermal current value
12…15 Reserved
*Only one out of bits 0…3, and one out of bits 9…11 can be on simultaneously.
The bit typically indicates the limit that is exceeded first.
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...