124 Parameters
Automatic
Automatic start guarantees optimal motor start
in most cases. It includes the flying start function
(starting into a rotating motor) and the
automatic restart function. The drive motor
control program identifies the flux as well as the
mechanical state of the motor and starts the
motor instantly under all conditions.
Note:
is set
, no flying start or automatic restart is
possible unless parameter
.
2
Defines the pre-magnetization time when
• parameter
(in vector motor control mode), or
is set to
(in scalar motor control mode).
After the start command, the drive automatically
premagnetizes the motor for the set time. To
ensure full magnetizing, set this parameter to
the same value as, or higher than, the rotor time
constant. If not known, use the rule-of-thumb
value given in the table below:
Note:
This parameter cannot be changed while
the drive is running.
500
0…10000 ms
Constant DC magnetizing time.
1 = 1
Selects the way the motor is stopped when a
stop command is received.
Coast
Stop by switching off the output semiconductors
of the drive. The motor coasts to a stop.
WARNING!
If a mechanical brake is used,
make sure that it is safe to stop the drive
by coasting.
0
Ramp
Stop along the active deceleration ramp. See
parameter group
page
page
1
No.
Name/Value
Description
Def/
FbEq16
Motor rated power Constant magnetizing
time
< 1 kW
> 50 to 100 ms
1 to 10 kW
> 100 to 200 ms
10 to 200 kW
> 200 to 1000 ms
200 to 1000 kW
> 1000 to 2000 ms
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...