Parameters 123
21
Start and stop modes.
Selects the motor start function for the vector
is set to
.
Notes
:
• The start function for the scalar motor control
• Starting into a rotating motor is not possible
when DC magnetizing is selected (
).
• With permanent magnet motors,
start mode must be used.
• This parameter cannot be changed while the
drive is running.
Fast
The drive pre-magnetizes the motor before start.
The pre-magnetizing time is determined
automatically, being typically 200 ms to 2 s
depending on motor size. This mode should be
selected if a high break-away torque is required.
0
Const time
The drive pre-magnetizes the motor before start.
The pre-magnetizing time is defined by
parameter
. This mode
should be selected if constant pre-magnetizing
time is required (e.g. if the motor start must be
synchronized with the release of a mechanical
brake). This setting also guarantees the highest
possible break-away torque when the pre-
magnetizing time is set long enough.
WARNING!
The drive will start after the set
magnetizing time has passed even if motor
magnetization is not completed. In applications
where a full break-away torque is essential,
ensure that the constant magnetizing time is
long enough to allow generation of full
magnetization and torque.
1
No.
Name/Value
Description
Def/
FbEq16
Содержание ACQ80
Страница 1: ... ABB DRIVES FOR WATER ACQ80 standard program control Firmware manual ...
Страница 2: ... Related documents are listed on page 13 ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 32: ...32 Startup control with I O and ID run ...
Страница 34: ...34 Using the control panel ...
Страница 74: ...74 Program features ...
Страница 78: ...78 Control macros ...
Страница 380: ...380 Fieldbus control through a fieldbus adapter ...
Страница 384: ...384 Parameterization with Drive Composer ...
Страница 388: ...388 Parameterization with Automation builder drive manager ...