Fieldbus control through the embedded fieldbus interface (EFB) 377
Status Word for the DCU Profile
The embedded fieldbus interface writes the drive Status Word bits 0 to 15 to the
fieldbus Status Word as is. Bits 16 to 32 of the drive Status Word are not in use.
Bit
Name
Value
State/Description
0
READY
1
Drive is ready to receive the start command.
0
Drive is not ready.
1
D
1
External run enable signal is active.
0
External run enable signal is not active.
2
Reserved for
D_TO_ROTATE
Not yet implemented.
3
RUNNING
1
Drive is modulating.
0
Drive is not modulating.
4
ZERO_SPEED
1
Drive is at zero speed.
0
Drive is not at zero speed.
5
ACCELERATING 1
Drive speed is increasing.
0
Drive speed is not increasing.
6
DECELERATING 1
Drive speed is decreasing.
0
Drive speed is not decreasing.
7
AT_SETPOINT
1
Drive is at setpoint.
0
Drive is not at setpoint.
8
LIMIT
1
Drive operation is limited.
0
Drive operation is not limited.
9
SUPERVISION
1
Actual value (speed, frequency or torque) is above a
limit. Limit is set with parameters 46.31…46.33
0
Actual value (speed, frequency or torque) is within
limits.
10
REVERSE_REF
1
Drive reference is in the reverse direction.
0
Drive reference is in the forward direction
11
REVERSE_ACT
1
Drive is running in the reverse direction
0
Drive is running in the forward direction
12
PANEL_LOCAL
1
Panel/keypad (or PC tool) is in local control mode.
0
Panel/keypad (or PC tool) is not in local control mode.
13
FIELDBUS_LOC
AL
1
Fieldbus is in local control mode.
0
Fieldbus is not in local control mode.
14
EXT2_ACT
1
External control location EXT2 is active.
0
External control location EXT1 is active.
15
FAULT
1
Drive is faulted.
0
Drive is not faulted.
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...