![ABB ACH580-34 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/abb/ach580-34/ach580-34_quick-installation-manual_2532009.webp)
Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet 9
Step-by-step drawings for an installation example of standard drive configuration in Rittal VX25 800 mm wide cabinet
INPUT
OUTPUT
U1
V1
W1
3
~
M
(PE) PE (PE)
3
4
5
6
7
9
L1
L2
L3
L1
L2
L3
1
2a
2b
PE
L1/
U1
V1
L2/ L3/
W1
UDC- UDC+
T1/
U2
T2/
V2
T3/
W2
PE
8
10
11
ACH580-34
1
2
3
Drive type
ACH580-34-
Air flow
Losses
Type DIN 43653
m
3
/h
W
U
N
= 400 V IEC
246A-4
2100
5280
170M5408
293A-4
2100
6400
170M5410
365A-4
2100
8000
170M6410
442A-4
2100
10000
170M6411
505A-4
2100
10000
170M6412
585A-4
2100
12600
170M6414
650A-4
2100
14200
170M6414
U
N
= 480 V IEC
246A-4
2100
5220
170M4410
293A-4
2100
5220
170M5408
365A-4
2100
7830
170M5410
442A-4
2100
9135
170M6410
505A-4
2100
9135
170M6411
585A-4
2100
9135
170M6411
650A-4
2100
10440
170M6412
U
N
= 480 V UL
240A-4
2100
5280
170M4410
302A-4
2100
6525
170M5408
361A-4
2100
7830
170M5410
414A-4
2100
9135
170M6410
477A-4
2100
10440
170M6411
WARNING!
The UDC+ and UDC- terminals of the drive
module must not be used for any other than optional external
brake chopper connection.
Содержание ACH580-34
Страница 1: ... ABB DRIVES FOR HVAC ACH580 34 drive modules Quick installation guide English 3 EN ...
Страница 8: ...8 EN Quick installation guide EN DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Страница 22: ...www abb com drives www abb com drivespartners 3AXD50000424627 Rev C MUL 2019 09 12 Contact us ...